MicroPower PAP800UL Operating Manual Download Page 3

Switched Mode Power Supply

Operating manual

PAP800UL

Perämiehenkatu 6, FIN 24100 Salo, Tel. +358 2 777 290, Fax +358 2 777 2918, [email protected], www.powerfinn.fi

Installation

1.

The   location   must   be   dry,   dust-free   and   indoor.   The   acceptable   full   power   temperature   range   is  
0°C…+50°C. Higher ambient temperature will limit the power (see curve). The power supply is not waterproof. Keep it dry
and away from areas with high humidity in order to avoid the risk for electrical shock and damages to the charger. 

2. The power supply can be installed horizontally or vertically. In case the power supply is mounted vertically with the

cable plate downwards, the floor and everything right below the power supply must be fire-resistant. Vertical mounting is
prohibited in case this condition cannot be met.

3. Leave at least 10 cm free space at both ends of the power supply to ensure sufficient ventilation.

When used as a charger, the charging process generates explosive hydrogen gas. Keep the area well ventilated Never use an
open flame or equipment that produce sparks close to the power supply and battery.

Wall mounting

Screw the assembly board to the wall using the mounting holes in the
back of  the board. Next, place the power  supply to the assembly
board and fasten it by using the small screws on the sides of the
board.

Charging operation

1. Ensure that the power supply is switched off and that the environment meets the conditions as described in

the previous section.

2. Connect the output cables to the load / battery terminals: + cable to the + terminal and – cable to the –

terminal

Note:

  Do   not   cut   the   output   cables.   In   case   the   cables   are   shortened,   the   output   voltage   is

overcompensated as much as the loss of voltage drops in the cable. The overcompensation may cause
voltage variations depending on the current consumption.

3. Turn the power on by turning the switch to position 1.

4. During normal power supply operation / charging process, the STATUS LED will light continuous orange.

5. To avoid sparking, turn off the power supply before disconnecting the cables.

DC Input connection

The power supply input cable is connected as follows:

L

negative or positive DC supply input

N

positive or negative DC supply input

PE

protective earth

The socket outlet shall be installed near the equipment and shall be easily accessible. Maximum 10A maximum
rating of protective device required in building installation. When having unearthed DC mains 2 fuses or 2 pole
circuit breaker required in building installation.