![Micropelt MLR003 User Manual And Device Specification Download Page 20](http://html1.mh-extra.com/html/micropelt/mlr003/mlr003_user-manual-and-device-specification_1788145020.webp)
Copyright Micropelt
Communication Profile MLR003RiEU61-07-1.1
–
20
8.2 FPORT 0x01 DOWNLINK: Controller / Network Server to MLR003RiEU61-07-1.1
BYTE
BIT
RANGE
SIZE
OFFSE
T
ABBREV.
DETAILS
1
DB0.7
…0.0
8
0
SPV
Set Point Value according to User Mode
VALVE %: 0x00 … 0x64 / 0 … 100%
Res = 1%
AMB TEMP: 0x00 … 0x50 / 0 … 40°C
0x00 = Default = 0x28 = 20°C
Res = 0,5°C
2
DB1.7
…1.0
8
8
RT
Room TMP from RCU °C
0x00 … 0xA0 / 0 … 40°C
0x00 = No Room TMP provided
Res = 0,25°C
3
DB2.7
…2.0
8
16
SSV
Set Safety Value according to safety mode
AMB TEMP: 0x00 … 0x50 / 0 … 40°C
0x00 = Default = 0x28 = 20°C
Res = 0,5°C
VALVE %: 0x00 … 0x64 / 0 … 100%
Res = 1%
4
DB3.7
1
24
RESERVED
DB3.6
…3.4
3
25
RCI
Radio Communication Interval
0b000 = Default = 10 minutes
0b000
10 minutes
0b001
5 minutes
0b010
60 minutes