Micropelt EnOcean MVA003E User Manual And Device Specification Download Page 22

MVA003E User manual and device specification 

 

 

 

Preliminary 

April 2019 

Page 21 of 24 

1DSMVA003E_0419v9e

 

11 Performance 

data 

Parameter 
 

Range 

 

Valve thread 

M 30 x 1,5 (adapter available for other types) 

Ambient operating temperature 

0 to 40°C, max 70% rH 

Flow pipe temperature 

75°C max 

Transportation & storage temperature 
range 

-20 to +65°C, max 70% rH 

Max pin stroke (calibration range) 

> 5 mm 

Operating pin stroke (0-100 %) 

2.5 mm typical 

Pin Stroke Resolution  
(defined by EnOcean Equipment Profile 
A5-20-01) 

Steps of 1% 

(smallest executable position change has to be 3% from 

current physical position) 

Adjustment speed 

0.95 mm/s typical 

Stall force 

100 N typical 

Noise level 

< 30 dB 

RF communication interval 

10 minutes 

Activation and debug RF  
communication interval  

~ 10 sec 

(will revert to the default 10 minutes after 10 minutes) 

Antifreeze 

Below 6ºC, open valve to 50%  

(referring to operating stroke) 

Safe position  
(following 6 consecutive communication 
failures) 

Internal temperature controller with last valid setpoint °C 

(SPS=1 operation), otherwise default value 21°C 

Will revert to standard operation as soon as radio 

communication is online again 

EnOcean EEP and operating mode 
 

A5-20-01  

Valve Pos. (%) or Setpoint Temperature (°C) 

EnOcean Remote management & 
Remote commissioning capability 

Yes  

 

DDF  
(Device description file/xml) 

Yes  

Please contact Micropelt 

Life cycle status and monitoring 
capabilities 

Yes  

 

Accuracy of internal ambient 
temperature sensor 

+/- 0.5 ºC  

  

Offset of internal ambient temperature 
sensor 

Default value = 3K  

 

Energy storage 
 

Construed for full year operation 

Energy generation minimum 
requirement 

90 standard heating days per year with T flow >45°C 

Battery voltage flag 

Battery voltage < 3.1 V 

RF communication interval will be set to 10 minutes 

Radio carrier frequency 

868.3 MHz 

Maximum radiated power 

+1.4 dBm (EN 300220-2:V3.1.1) 

Receiver 

Category 2 (EN 300 220-1 V3.1.1) 

Conformity CE 

 

 

Summary of Contents for EnOcean MVA003E

Page 1: ...r EH4 Germany Brand Micropelt Document number 1DSMVA003E_0419v9e Wireless heating valve actuator MVA003E EnOcean User manual and device specification EnOcean Equipment Profile A5 20 01 Annex List of a...

Page 2: ...rotocol Data Overview 13 8 2 Description of individual functions 14 8 2 1 Setpoint Selection DB1 2 RCU to MVA003E 14 8 2 2 Valve position and Setpoint temperature C DB3 RCU to MVA003E 14 8 2 3 Summer...

Page 3: ...umentation v7e Released 24 11 2017 Safety position Internal temperature control 21 C instead of 50 valve position no change to radio communication interval v8e Released 04 04 2019 New product code MVA...

Page 4: ...unit to environmental stress such as high mechanical forces do not step on it strong vibrations direct sunlight or extreme temperatures The unit must not be disassembled or modified In case you are un...

Page 5: ...to mounting position to switch off The MVA003E unit does have a built in motor error detection ACO The ACO bit does signal incomplete or unsuccessful reference runs from mounting motor issues during n...

Page 6: ...ble MVA003E is designed for low power operation Therefore must Remote Commissioning ReCom commands be executed within an 8 seconds time period after the UNLOCK command ReCom can be used to set its lin...

Page 7: ...ed to allow operation through 365 days per year when used in typical radiator heating installations If in exceptional cases the storage voltage drop below a certain limit the actuator reports this sta...

Page 8: ...inutes One hour after this action the pushbutton switch will lock and can only be unlocked by performing RESET Success Radio communication Failure 3x red flash unit returns to mounting position OFF Un...

Page 9: ...ESET from mounting position Push and hold the button for at least 10 seconds Unit moves the plunger fully in and sets inner stop reference anew then turns off remaining in mounting position After 10 s...

Page 10: ...ocessorRestart Motor executes reference run Motor movesto mountingposition 3x red LED novalve detected Motor movesback to mountingposition Device is 1x red LED reference runcorrect Device isin normal...

Page 11: ...ication interval defaults to 10 minutes Success Single red flash Failure 6x red flash Motor or gear error 3 Execute Remote Commissioning operations Start ReCom operations with a valid UNLOCK command e...

Page 12: ...BS Telegram UNLOCK 0x0001 SET LINK TABLE 0x0212 GET LINK TABLE 0x0211 SET DEVICE CONFIG 0x0231 GET DEVICE CONFIG 0x0230 GET PRODUCT ID 0x0227 LOCK 0x002 MAX TIME WINDOW BETWEEN UNLOCK AND LOCK 8 SECON...

Page 13: ...t Typ 30 m range in passages up to 100 m in halls Plasterboard and wood walls Typ 30 m range through max 5 walls Brick and foamed concrete walls Typ 20 m range through max 3 walls Reinforced concrete...

Page 14: ...t be set to 0x00 DB2 6 ENIE Active energy harvesting valve is hot DB1 7 DB1 4 Not used set to zero DB2 5 ES Energy storage sufficiently filled DB1 3 SB Summer mode transmit receive time interval 8 hou...

Page 15: ...eceives the status message Summer mode ON from the controller then the valve transmit receive interval is increased 10 minutes to 8 hours It is possible to wake up the iTRV through 1 x pressing the pu...

Page 16: ...0 0x04 o DB1 3 0 regular default radio cycle no summer mode o DB1 2 1 DB3 7 DB3 0 is set to internal temp controller with default duty cycle Summer bit not active DB0 7 DB0 0 0x08 Data telegram 1 Setp...

Page 17: ...lve temperature setpoint 20 1 C DB2 7 0 81 10000001 129 TMP Temperature from controller gateway 19 8 C DB1 7 0 04 00000100 4 RIN DB1 7 0 0 Normal operation 1 Initiate run in sequence of actor LFS DB1...

Page 18: ...e only inbound relationships are not supported Manually erasing the outbound link table is not possible Manual pairing teach in however overwrites the first entry of the outbound link table clearing t...

Page 19: ...tadata Query Response Get Link Table Query Response Set Link Table Content Configuration Parameters Bundle Get Device Configuration Query Response Set Common Configuration Query RESET DEVICE DEFAULTS...

Page 20: ...00 0 Auto 2 5 10 minutes 0x01 1 10sec for debugging only 0x02 2 2min 0x03 3 5min 0x04 4 10 min DEFAULT 0x05 5 20min 0x06 6 30min Automatic mode 2 5 10 minutes interval based flow temperature and inter...

Page 21: ...eling of each valve actuator is according the EnOcean alliance QR Code specification which does include EURID EnOcean Unique Radio Identifier as well as device product ID In addition to such mandatory...

Page 22: ...valve to 50 referring to operating stroke Safe position following 6 consecutive communication failures Internal temperature controller with last valid setpoint C SPS 1 operation otherwise default val...

Page 23: ...ion Preliminary April 2019 Page 22 of 24 1DSMVA003E_0419v9e Mechanical Interface to Radiator Valve The MVA003E is designed to mount onto an M30 x 1 5mm radiator valve bodies Several other valve types...

Page 24: ...5 Item no 9704 24 700 Danfoss RA2000 Item no MVA Adapter RA2 Adapter Oventrop M30 x 1 0 Item no 9700 10 700 Adapter Comap M28 x 1 5 Item no 9700 55 700 Danfoss RAV Item no 9800 24 700 Danfoss RAV L 26...

Page 25: ...1DSMVA003E_0419v9e 13 Annex 2 Theft protection Pls contact Micropelt to receive more information about MVA DS01 used without Adapter and MVA DS02 used with adapter theft protection solution Stainless...

Reviews: