MVA003E User manual and device specification
Preliminary
April 2019
Page 19 of 24
1DSMVA003E_0419v9e
9.5 ReCom supported MVA internal parameter
Parameter INDEX
Description
Ambient to target temp offset [K]
0
(0x00) 0 … Auto *1
(0x01) 1 … -3 K
(0x02) 2 … -2 K
(0x03) 3 … -1
(0x04) 4 … 0 K
(0x05) 5 … +1 K
(0x06) 6 … +2 K
(0x07) 7 … +3 K
(DEFAULT)
…
(0x0F) 15 … +11 K
* Only available when flow sensor is available
Radio communication interval
[s/min]
1
(0x00) 0…Auto * (2/5/10 minutes)
(0x01) 1 … 10sec (for debugging only)
(0x02) 2 … 2min
(0x03) 3 … 5min
(0x04) 4 … 10 min
(DEFAULT)
(0x05) 5 … 20min
(0x06) 6 … 30min
* Automatic mode 2/5/10 minutes interval based flow
temperature and internal storage is only available
when flow sensor is available. MVA003E default is 10
minutes
Execute Reference Run
10
0x01
DEFAULT 0x00
Temp.-control loop gain
parameter
12
(0x00 … 0xFF) 0 … 255 = 10x GAIN
DEFAULT 30 = 0x1E
Battery open circuit voltage (V)
13
READ ONLY
(0x00 … 0xFF) 0 … 255 = 10x Voltage
Example 0x21 = DEZ 33 : 10 = 3,3Volt
Please contact Micropelt to receive related xml (DDF) file with further technical details.