April 2019 Author: EH4; Germany / Brand Micropelt - Document number 1DSMVA003E_0419v9e

 

 

 
 
 
 
 
 

Wireless heating valve actuator 

MVA003E EnOcean 

 

User manual and device specification 

EnOcean Equipment Profile A5-20-01 

Annex: List of adapters and theft protection 

 
 
 

 

 

 
 
 
 
 
 

Summary of Contents for EnOcean MVA003E

Page 1: ...r EH4 Germany Brand Micropelt Document number 1DSMVA003E_0419v9e Wireless heating valve actuator MVA003E EnOcean User manual and device specification EnOcean Equipment Profile A5 20 01 Annex List of a...

Page 2: ...rotocol Data Overview 13 8 2 Description of individual functions 14 8 2 1 Setpoint Selection DB1 2 RCU to MVA003E 14 8 2 2 Valve position and Setpoint temperature C DB3 RCU to MVA003E 14 8 2 3 Summer...

Page 3: ...umentation v7e Released 24 11 2017 Safety position Internal temperature control 21 C instead of 50 valve position no change to radio communication interval v8e Released 04 04 2019 New product code MVA...

Page 4: ...unit to environmental stress such as high mechanical forces do not step on it strong vibrations direct sunlight or extreme temperatures The unit must not be disassembled or modified In case you are un...

Page 5: ...to mounting position to switch off The MVA003E unit does have a built in motor error detection ACO The ACO bit does signal incomplete or unsuccessful reference runs from mounting motor issues during n...

Page 6: ...ble MVA003E is designed for low power operation Therefore must Remote Commissioning ReCom commands be executed within an 8 seconds time period after the UNLOCK command ReCom can be used to set its lin...

Page 7: ...ed to allow operation through 365 days per year when used in typical radiator heating installations If in exceptional cases the storage voltage drop below a certain limit the actuator reports this sta...

Page 8: ...inutes One hour after this action the pushbutton switch will lock and can only be unlocked by performing RESET Success Radio communication Failure 3x red flash unit returns to mounting position OFF Un...

Page 9: ...ESET from mounting position Push and hold the button for at least 10 seconds Unit moves the plunger fully in and sets inner stop reference anew then turns off remaining in mounting position After 10 s...

Page 10: ...ocessorRestart Motor executes reference run Motor movesto mountingposition 3x red LED novalve detected Motor movesback to mountingposition Device is 1x red LED reference runcorrect Device isin normal...

Page 11: ...ication interval defaults to 10 minutes Success Single red flash Failure 6x red flash Motor or gear error 3 Execute Remote Commissioning operations Start ReCom operations with a valid UNLOCK command e...

Page 12: ...BS Telegram UNLOCK 0x0001 SET LINK TABLE 0x0212 GET LINK TABLE 0x0211 SET DEVICE CONFIG 0x0231 GET DEVICE CONFIG 0x0230 GET PRODUCT ID 0x0227 LOCK 0x002 MAX TIME WINDOW BETWEEN UNLOCK AND LOCK 8 SECON...

Page 13: ...t Typ 30 m range in passages up to 100 m in halls Plasterboard and wood walls Typ 30 m range through max 5 walls Brick and foamed concrete walls Typ 20 m range through max 3 walls Reinforced concrete...

Page 14: ...t be set to 0x00 DB2 6 ENIE Active energy harvesting valve is hot DB1 7 DB1 4 Not used set to zero DB2 5 ES Energy storage sufficiently filled DB1 3 SB Summer mode transmit receive time interval 8 hou...

Page 15: ...eceives the status message Summer mode ON from the controller then the valve transmit receive interval is increased 10 minutes to 8 hours It is possible to wake up the iTRV through 1 x pressing the pu...

Page 16: ...0 0x04 o DB1 3 0 regular default radio cycle no summer mode o DB1 2 1 DB3 7 DB3 0 is set to internal temp controller with default duty cycle Summer bit not active DB0 7 DB0 0 0x08 Data telegram 1 Setp...

Page 17: ...lve temperature setpoint 20 1 C DB2 7 0 81 10000001 129 TMP Temperature from controller gateway 19 8 C DB1 7 0 04 00000100 4 RIN DB1 7 0 0 Normal operation 1 Initiate run in sequence of actor LFS DB1...

Page 18: ...e only inbound relationships are not supported Manually erasing the outbound link table is not possible Manual pairing teach in however overwrites the first entry of the outbound link table clearing t...

Page 19: ...tadata Query Response Get Link Table Query Response Set Link Table Content Configuration Parameters Bundle Get Device Configuration Query Response Set Common Configuration Query RESET DEVICE DEFAULTS...

Page 20: ...00 0 Auto 2 5 10 minutes 0x01 1 10sec for debugging only 0x02 2 2min 0x03 3 5min 0x04 4 10 min DEFAULT 0x05 5 20min 0x06 6 30min Automatic mode 2 5 10 minutes interval based flow temperature and inter...

Page 21: ...eling of each valve actuator is according the EnOcean alliance QR Code specification which does include EURID EnOcean Unique Radio Identifier as well as device product ID In addition to such mandatory...

Page 22: ...valve to 50 referring to operating stroke Safe position following 6 consecutive communication failures Internal temperature controller with last valid setpoint C SPS 1 operation otherwise default val...

Page 23: ...ion Preliminary April 2019 Page 22 of 24 1DSMVA003E_0419v9e Mechanical Interface to Radiator Valve The MVA003E is designed to mount onto an M30 x 1 5mm radiator valve bodies Several other valve types...

Page 24: ...5 Item no 9704 24 700 Danfoss RA2000 Item no MVA Adapter RA2 Adapter Oventrop M30 x 1 0 Item no 9700 10 700 Adapter Comap M28 x 1 5 Item no 9700 55 700 Danfoss RAV Item no 9800 24 700 Danfoss RAV L 26...

Page 25: ...1DSMVA003E_0419v9e 13 Annex 2 Theft protection Pls contact Micropelt to receive more information about MVA DS01 used without Adapter and MVA DS02 used with adapter theft protection solution Stainless...