2.3 - Algorithms of the different functions
2.3.1 - Setting range of the reference input quantities
System frequency
:
Fn
= (50-60)Hz
Rated primary current of phase C.Ts.
:
In
= (0-9999)A, step 1A
Rated primary current of ground C:T.
:
On
= (0-9999)A, step 1A
Rated secondary phase-to-phase voltage of P.Ts.
:
Uns
= (100-125)V, step 1V
Relay basic current (Generator’s rated current)
:
Ib
= (0.5-1.1)In, step 0.1In
2.3.2 - F50/51 - Dual level 3-phase overcurrent
F1 - 50/51
: Low set overcurrent
Pick-up (operation) level
Setting
I>
= Dis blocks function’s operation
:
I>
= (1-2.5)Ib, step 0.01Ib
Drop-out ratio
:
0.95
Minimum operation time of instantaneous output
: 30ms
Trip time delay in the definite time operation mode
F(I>) = D
: t =
tI>
= (0.05-30)s, step 0.01s
Trip time delay in the inverse time operation mode
F(I>) = SI
1
)
(I/I
tI
0.033
t
0.02
(tI> = trip time delay at I/I> = 5)
(see curves TU0311 Attachment. B)
F2 50/51
: High set overcurrent
Pick-up (operation) level
Setting
I>>
= Dis blocks function’s operation
:
I>>
= (1-12)Ib, step 0.1Ib
Drop-out ratio
:
0.95
Minimum operation time of the instantaneous element
: 30ms
Independent trip time delay
: t =
tI>>
= (0.05-3)s, step 0.01s
2.3.3 - F50/51G - Stator Ground Fault
Pick-up (operation) level
Setting
O>
= Dis. blocks function’s operation
:
O>
= (0.02-0.4)On, step 0.01On
Drop-out ratio
:
0.95
Minimum operation time of the instantaneous element
: 30ms
Independent trips time delay
: t =
tO>
= (0.05-30)s, step 0.01s