i.  When the Eskom power is flowing through the UPS it keeps the voltage at a constant 

220volts not allowing fluctuations in the Eskom power to affect the ATM. 

ii.  When load shedding occurs the UPS seamlessly shifts across to battery power keeping the 

ATM operational for a certain time frame. (load dependent) 

iii.  The battery system is a 24volt system. 

iv.  Due to the batteries not being deep cycle batteries the software on the ATM shuts the UPS 

down at 20volts. This equates to at least 90% of the power generated by the batteries. 

v.  Once the batteries have shut down the UPS goes into a standby mode. This allows the UPS 

to save the remaining voltage in the batteries. 

vi.  Once Eskom returns the UPS automatically starts up and commences in the powering up of 

the ATM. 

vii.  The batteries should thus never be allowed to discharge completely. 

 

1.2 

Key Features

 

1.    Compatible with both linear and non-linear load. 
2.    24 hours operation on the UPS. 
3.    DC start and automatic self-diagnostic function. 
4.    High Power 3 stage Charger 
5.    High efficiency design to save electricity. 
6.    Low heat dissipation in long time operation. 
7.    Design to operate under harsh environment. 

 

1.3 

Important Notices 

 

Read instructions carefully before operating Inverter. 

 

Inverter connection instructions must be followed. 

 

The unit should only be opened by skilled personal. 

 

Retain the load within in the rating of the UPSr to prevent Overload/Short Circuit. 

 

Keep The UPS Clean & Dry. 

2. 

SAFETY INSTRUCTION 

 

2.1 

Positioning 

1.  Do not put the Inverter on rugged or inclined surface. 
2.  Do not install the UPS near water or in damp environments. 
3.  Do not block off ventilation openings in the UPS housing and don’t leave objects on 

top of the UPS. 

4.  Keep the UPS far away from heat emitting sources. 
5.  Do not expose it to corrosive gas. 
6.  Ambient temperature: 0˚C - 40˚C. 

 

2.2 

Maintenance and Service 

1.  Caution – Risk of Electric Shock.    
2.  Batteries may cause electric shock and have a high short-circuit current. Please 

take the precautionary measures specified below and any other measures 
necessary when working with batteries. 

  Remove wristwatches, rings and other metal objects. 

  Use only tools with insulated grips and handles. 

Summary of Contents for 1kW24V

Page 1: ...0 1Kw24V UPS Manual...

Page 2: ...1 Contents 1 INTRODUCTION 2 2 SAFETY INSTRUCTION 2 3 SYSTEM DESCRIPTION 3 4 UPS OPERATION 4 5 UPS PROGRAMMING 9 5 FAULT TROUBLE SHOOTING 18...

Page 3: ...self diagnostic function 4 High Power 3 stage Charger 5 High efficiency design to save electricity 6 Low heat dissipation in long time operation 7 Design to operate under harsh environment 1 3 Importa...

Page 4: ...3 2 3 DOWN Key Use to move the display down 3 2 4 ENTER Key It is pressed with the UP Key to turn on the UPS Push the ENTER button to confirm or store DATA 3 2 5 Push the UP and DOWN keys together to...

Page 5: ...ay then changes to The display then changes to UPS TURNED OFF CALIBRATING MICROCARE ON OFF ENTER Menu Down Menu Up OK Inverter Error MICROCARE 1 KW OUTPUT LOW MICROCARE ON OFF ENTER Menu Down Menu Up...

Page 6: ...l change to indicate the amount of LOAD as a of the UPS unit being used in KW When the Up key and the Down Key are pressed simultaneously for 3 seconds the UPS will be turned Off LCD DISPLAY MENU With...

Page 7: ...UPS is drawing from the battery If the battery Amps changes to CHR AMPS This shows the Charge Amps that are being put back into the battery bank from the charging source MICROCARE 1 KW OUTPUT 20 MICR...

Page 8: ...draw from the grid power supply This shows the internal temperature of the UPS TEMPERATURE COOL MICROCARE ON OFF ENTER Menu Down Menu Up OK Inverter Error UPS VOLTS 222 UPS AMPS 7 0 MICROCARE ON OFF E...

Page 9: ...umber of the Inverter The Serial number of the inverter needs to be noted and supplied when requesting any fault support information SERIAL NUMBER MCxx007 MICROCARE ON OFF ENTER Menu Down Menu Up OK I...

Page 10: ...Push ENTER if you want to change the set up menu By pushing ENTER button you can change whether the inverter runs in NORMAL SENSE mode or SOLAR CONTROL mode NORMAL SENSE is to be selected whenever usi...

Page 11: ...nstantly with mains fail prediction 8mS SOFTSTART Default 8 milli second transfer time and will ramp the RMS voltage up in less than 1 second with mains fail prediction GEN SOFTSTART 8 milli second tr...

Page 12: ...ter a medium delay time period HIGH 3x RESET High sensitivity to short circuits will trip the inverter after a short delay time period with soft start to prevent in rush current MED 3x RESET Medium se...

Page 13: ...will then change to The settings available are as follows NO DELAY As soon as Grid power is available the Inverter will synchronise and switch from battery to Grid DELAY 30Sec 30 seconds after Grid po...

Page 14: ...display will show EXIT DO NOT SAVE SET UP MENU MICROCARE ON OFF ENTER Menu Down Menu Up OK Inverter Error RESTORE FACTORY SET UP MENU MICROCARE ON OFF ENTER Menu Down Menu Up OK Inverter Error EXIT AN...

Page 15: ...how If no entry is made for 1 minute the display will return to the main menu Use the UP DOWN button to select BATTERY menu Push ENTER to access the Battery Setup Menu SAVING DATA TO INTERNAL MENU MIC...

Page 16: ...5 of charge rate as per the list supplied below INVERTER CHARGE AMPS 1Kw24V 30A In regards to the battery charge level The Level selected will allow the battery charge to the batteries 25 OF RATED CHR...

Page 17: ...UP button The menu will then change to This allows the user to select the TIME that the BOOST VOLTAGE will be held at before changing to FLOAT By pushing ENTER you can select 1 2 or 3 hours BATTERY B...

Page 18: ...s If the charger is in FLOAT but you require it to go back into BOOST then the next menu will allow this Pushing the ENTER button allows the charge to be changed from AUTO to BOOST or FLOAT Push the U...

Page 19: ...tteries 10 The UPS LCD display should state Please wait 11 The LCD display then states UPS Turned Off Calibrating 12 The LCD display then states UPS Turned Off 13 Then depress the center button green...

Page 20: ...he re connection procedure listed above d If the ATM has any liquid damage or lightning strikes please log a fault report e Should the UPS still remain non operational once the power has been re conne...

Page 21: ...erminals When considering any electronic breakage except due to lightning reverse polarity over voltage etc the state of the internal control circuitry determines the warranty This warranty will not a...

Page 22: ...items purchased from J J Electronics and we require the following information 1 Details of the item s you would like to return 2 Our invoice number 3 The reason for the return 4 J J Electronics must...

Reviews: