PARAMETERS FOR MDD58W THERMOSTAT
PARAMETER
DESCRIPTION
FOR BLUE
DISPLAY
FOR RED
DISPLAY
SEt
Set point
42
55
Hy
Differential
10
5
LS
Minimum set point
40
55
US
Maximum set point
48
60
ot
Thermostat probe calibration
8
5
P2
Evaporator probe presence
n
n
oE
Evaporator probe calibration
0
0
od
Outputs activation delay at start up
3
3
AC
Anti-short cycle delay
1
1
Cy
Compressor ON time with faulty probe
6
6
Cn
Compressor OFF time with faulty probe
12
30
CF
Temperature measurement units
F
F
rE
Resolution (only for °C)
in
in
Ld
Default display
P1
P1
dy
Display delay
5
2
dE
Defrost termination temperature
50
60
id
Interval between defrost cycles
8
0
Md
Maximum length for defrost
15
1
dF
Display during defrost
sp
sp
AU
Maximum temperature alarm
99
99
AL
Minimum temperature alarm
-50
-50
Ad
Temperature alarm delay
15
15
dA
Exclusion of temperature alarm at startup
90
90
d2
Second probe display
0
0
Pt
Parameter table code (readable only)
5
5
rL
Firmware release (readable only)
0
0