13
©2022 Micro-Air Corp
March 21, 2022, revision 1.0
Auto Gas Changeover
this feature.
Auto Gas Changeover operation
mirrors the OEM thermostat’s operation for
additional stages of heat
when the thermostat determines more are needed. The three escalating stages are shown in
. All
three stages may not be available based on your system, but EasyTouch will output the same logic. Stage
2 heating is available in every system.
Staging
Heat Source
Stage 1
Heat Pump
Stage 2
Furnace 1
Stage 3
Furnace 2
Table 8 - Heat Staging
Heat Pump and Auto Cool/Heat Pump Changeover Behavior
shows how Auto Gas Changeover affects the Heat Pump operational modes when enabled.
Environment
Operation
Inside 4° Or Less Below Setpoint Normal Heat Pump Operation (Stage 1)
Inside 5° Or 6° Below Setpoint
Stage 1 and Stage 2 Run Until Setpoint is Satisfied
Inside 7° Or More Below Setpoint
Stage 1, Stage 2, and Stage 3 Run Until Setpoint is Satisfied
or
Any Stage Runs 20 Minutes
Stage Escalates to the Next Highest Available Stage
3 Cycles in a Row Call for Escalation
Operates on
Behavior for Two Hours
Table 9 - Heat Pump AGC Operation
Note:
operation may be different based on the Gap settings. See section
for details.
Furance and Auto Cool/Furnace Changeover Behavior
shows how Auto Gas Changeover affects the Furnace operational modes when enabled.
Environment
Operation
Inside 4° Or Less Below Setpoint Normal Furnace Operation (Stage 2) (Stage 1 Never Runs)
Inside 5° Or More Below Setpoint
Stage 2 and Stage 3 Run Until Setpoint is Satisfied
or
Any Stage Runs 20 Minutes
Stage Escalates to the Next Highest Available Stage
3 Cycles in a Row Call for Escalation
Stage 2 and Stage 3 will Start Together for Next Two Hours
Table 10 - Furnace AGC Operation
operation may be different based on the Gap settings. See section
for details.