15
• Timer to close: Closes the door from mid-stop or full open. Momentary activation of stop button will de-activate the timer.
When door is closing, momentary activation of safety devices will reverse the door to mid-stop (if enabled) or full open and
de-activates the timer. Timer resumes its normal operation upon momentary activation of open push button or once the close
cycle is completed. If mid-stop is enabled and “Timer from mid-stop only” dip-switch is ON, timer is enabled only from mid-
stop and disabled from full open. If mid-stop is enabled and “Timer from mid-stop only” dip-switch is OFF, timer is enabled
from full open and mid-stop.
TS: (Momentary on open and close, timer to close secure, STOP BUTTON DISABLES TIMER)
• Open Button: Momentary activation opens the door. When door is closing, momentary activation reverses the door.
Momentary contact from mid-stop opens the door to full open position. Momentary contact at full-open refreshes the timer if
enabled at full open. Momentary contact at full open position re-activates the timer if timer has been disabled previously by
stop button. Constant activation when door is opening, bypass mid-stop if enabled.
• Close button: Momentary on close.
• Stop button: If door is opening or closing, momentary activation stops the door. Momentary
activation while timer is counting at mid-stop or full open de-activates the timer.
• Single button device, single channel transmitter and 3-channel (1,2,3) radio transmitter:
SEQUENTIAL FUNCTION: Open/Stop/Close/Reverse.
COMMERCIAL FUNCTION: Open/Reverse/Refresh timer.
• 3-button O/C/S radio transmitter: Same as open, close, stop buttons.
• Safety Devices: When door is closing, momentary activation reverses the door. Momentary
activation refreshes the timer to close.
• Timer to close: Closes the door from mid-stop or full open. Momentary activation of stop button will de-activate the timer.
Timer resumes its normal operation upon momentary activation of open push button or once the close cycle is completed.
If mid-stop is enabled and “Timer from mid-stop only” dip-switch is ON, timer is enabled only from mid-stop and disabled
from full open. If mid-stop is enabled and “Timer from mid-stop only” dip-switch is OFF, timer is enabled from full open and
mid-stop.
Warning: When replacing the logic board in a single-phase operator,
Make sure that Jumper 2 is installed properly before operating the door.
Failure to do this will damage the logic board.
PROGRAMMING INSTRUCTIONS:
NOTE: ALL PROGRAM FUNCTIONS CAN BE INITIATED BY TURNING THE SELECTOR SWTICH TO THE
DESIRED SETTING AT ANY POINT DURING OPERATION EXCEPT FOR THE MID STOP and RUN TIMER
MODE,PROGRAMMING MUST START FROM THE FULL CLOSED POSITION.
RUN-TIMER SETUP:
Run-timer is the maximum amount of time the motor will run upon receiving an open
or close command. The factory default value for run-timer is 45 seconds.
Note: Limits must be set prior to setting run timer.
Modify the run-timer from factory default:
1. Close the door to full close position.
2. Set the selector dial to “Run-timer” position. The “Delay On Close Timer”
LED should blink.
3. Press open button. Wait until door reaches full open position. The run timer value is set
to the time taken for the door to travel from full close position to full open position plus 5 seconds.
4. Set the selector dial to the desired mode of operation.
Modify the run-timer to factory default:
1. Close the door to full close position.
2. Set the selector dial to “Run-timer” position.
3. Press stop button. The run-timer is modified to the factory default value. Then set the selector dial to the desired
mode of operation.
Summary of Contents for Pro-APTC
Page 1: ...installation instruction manual Serial Installation Date Wiring Diagram PRO APTC...
Page 28: ...MICANAN Commercial Door Opening Devices 3 1 2 4 5 6...
Page 29: ...MICANAN Commercial Door Opening Devices 4 1 2 3 5 6...
Page 30: ...MICANAN Commercial Door Opening Devices 4 1 2 3 5 6...
Page 31: ...Notes...