WTR Automatic Backwash Series Operator's Manual
13
7. Install the three floats in the
Sump Pit
. Allow a 2" tether and enough room for them to move freely without interfering
with the plumbing.
a. Float #1 Blue: Pit low level shut-off. Attach this float 10" above the inlet.
b. Float #4 Red: Fresh water makeup. Height of this float must be adjusted to the individual pit system.
c. Float #5 Blue: Rain water overflow. Height of this float must be adjusted to the individual pit system.
NOTE:
The above information is for reference only. Professional installers or architects may use this guideline to
meet specific site requirements.
WARNING RISK OF ELECTROCUTION! TO REDUCE THE RISK OF ELECTROCUTION, KEEP ALL
CONNECTIONS DRY AND OFF THE GROUND.
INSTALLATION