14
Stationary Electric Air Compressor Manual
ELECTRICAL
1. A qualified electrician MUST hook up the electrical system.
a. Verify the electrical supply at the power source is off.
b. Be certain all switches on the Control Panel and Pressure Switch are in the "OFF" position.
c. Make connections to the terminal as shown below.
DANGER RISK OF ELECTROCUTION!
IMPROPER CONNECTION OF THE EQUIPMENT-GROUNDING CONDUCTOR CAN RESULT IN
A RISK OF SHOCK OR ELECTROCUTION. CHECK WITH A QUALIFIED ELECTRICIAN OR
SERVICE PERSONNEL IF YOU ARE IN DOUBT AS TO WHETHER THE OUTLET IS PROPERLY
GROUNDED. THE WIRE WITH INSULATION HAVING AN OUTER SURFACE THAT IS GREEN
WITH OR WITHOUT YELLOW STRIPES IS THE GROUNDING WIRE.
WARNING RISK OF ELECTRICAL SHOCK!
THIS PRODUCT MUST BE GROUNDED. IF THERE SHOULD BE A MALFUNCTION OR
BREAKDOWN, GROUNDING PROVIDES A PATH OF LEAST RESISTANCE FOR ELECTRIC
CURRENT TO REDUCE THE RISK OF ELECTRIC SHOCK.
PRE-START CHECKLIST:
1. Check oil level. Add if necessary.
a. For proper lubrication the compressor shall not be operated
below the minimum or above the maximum RPM recommended
for the various models.
b. Maintain oil level mid-way between the upper and lower lines of
the crankcase sight gage. Note the illustration:
c. Stop compressor to add and gauge oil.
d. Do not fill above the upper line and do not operate compressor with oil level below the lower line.
e. Change oil at the first 100 hours of operation and 1000 hours thereafter, or as required. It may be
ELECTRIC DIAGRAM INDUSTRIAL LINE
L1
L2
L3
G
L2
L1
Power
In
L1
L2
L3
G
L2
L3
L1
Power
In
1 Phase
3 Phase
PREPARATION INSTRUCTIONS
Proper Oil Level
Oil Gauge