STRATA1
19.1.1 dip switch
settings
OFF
No Mixing Valve Control Fitted
or
OFF
No Outside Air Sensor Fitted
OFF
Modulating Room Unit Installed
OFF
Analogue Unit 0-3V
OFF
Cascade not fitted
ON
Cascade controls fitted
OFF
* Room unit as Remote Control ONLY
* Remote = Room unit with temperature
sensor turned off and unit acting
just as a remote controller
Room unit with temperature sensor active
ON
PWM Unit (RE2132)
ON
* Room unit with Sensor
OFF
Pump
ON
Divertor valve
OFF
No External
controls
(Method of charging DHW cylinder)
ON
On/off
Room Stat
Time Clock
OFF
0-3 volt control or
0-10 volt control
via adaptor
ON
PWM
cascade
(KKM2)
ON
No external controls fitted.
On/Off controls fitted.
Cascade controls for multiple boilers.
ON
Outside Air Sensor Fitted
OFF
Radiator Circuit (mt 70/50ºC)
OFF
1 x Room Unit (RE2132)
(wired directly to the boiler)
ON
2 x Room Units (RE2132)
Off Off Remote / Remote
On Off Sensor / Remote *
On On Sensor / Sensor
Dip Switches 3 & 4
ON
Radiator Circuit (ht 85/65ºC)
ON
Underfloor Zone Mixing Valve Control Fitted (MR03)
Dip Switches 6 & 7
(system operating temperature)
Dip Switch 6
Dip Switch 2
Dip Switch 5
Dip Switch 4
Dip Switch 4
Dip Switch 4
Dip Switch 5
Dip Switch 1
Dip Switch 3
Dip Switch 8
Dip Switch 7
6
OFF
7
OFF
Low Temp 55/45ºC
6
OFF
7
ON
Med Temp 70/50ºC
6
ON
7
OFF
High Temp 85/65ºC
6
ON
7
ON
High Temp 85/65ºC
3
4
Sensor=