23
STRATA1
16.0 ventilation requirements single appliances (contd)
Table 6
Compartment Installation - Room sealed flue
Natural Ventilation direct to outside air.
Boiler Model
Ventilation Openings Free Area cm
2
High Level
Low Level
Strata 1/45
215
215
Strata 1/60
285
285
Strata 1/75
360
360
Table 7
Compartment Installation - Room Sealed Flue
Natural Ventilation from Adjacent Room
Boiler Model
Ventilation Openings Free Area cm
2
High Level
Low Level
Strata 1/45
430
430
Strata 1/60
570
570
Strata 1/75
Ventilation from adjacent room not permitted - See Table 1 above.
Multiple Appliances Installed in the Same Room or Space
Where multiple Strata 1 boilers are installed in the same room or space then
the aggregate of the appliance inputs must be taken to determine (from the
following data) the amount of ventilation required.
Appliance gross heat inputs should be taken as:-
Strata 1/45
= 50.34 kW
Strata 1/60
= 60.20 kW
Strata 1/75
= 81.41 kW
Table 8
Non Room Sealed Flue Installations
Natural Ventilation Direct to Outside Air.
Low Level (Inlet):
540cm
2
plus 4.5cm
2
per kW in excess of 60kW total rated input.
High Level (Outlet):
270cm
2
plus 2.25cm
2
per kW in excess of 60kW total rated input.
Table. 9
Room Sealed Flue Installations
Natural Ventilation Direct to Outside Air
(Ventilation recommended for cooling purposes)
Low Level (Inlet): 4.5cm
2
per kW of total rated input.
High Level (Outlet): 4.5cm
2
per kW of total rated input.