Heating Pump
2A. Max
HWS Primary
Pump
2A. Max
Hot Water
Calorifier or
Indirect Cylinder
Low Velocity
Mixing Header
Max Velocity 0.5m/s
Expansion
Vessel
Filling
Point
CWM
Strainer
Strainer
Condense
Waste
Strata 1
Boiler
Strata 1
Boiler
Strata 1
Boiler
KKM 2
Heating Load
IV
IV
IV
IV
PS
1*
17.0 hydraulic system
design
OS=
Outside air temperature sensor, used where
direct-on-boiler weather compensated flow
temperatures are required.
C=
Room temperature controls e.g. RE2132
modulating room unit from MHS Boilers, or,
separate time clock & room thermostat.
FS=
Flow temperature sensor
RS=
Return temperature sensor
S=
Hot water temperature sensor or
thermostat
KKM2=Modulating Kaskade Manager. Up to 9Nr
boilers may be controlled using 2Nr linked
KKm2's.
PS=
Low water pressure cut off switch
*1=
Filling Point. In accordance with BS 6644,
automatic pressurisation unit must be
installed when the boilers input is greater
than 60kW.
See item 17.1
Typical Multiple Strata 1 installation. Boilers controlled by modulating Kaskade manager which also has
the facility to control heating & domestic hot water production. Heating flow temperature may be
fixed/constant or weather variable. Hot water has priority.
System Type 6