9.2 error correction list
The error correction list contains possible causes as well as information about the elimination of
the fault.
Line Number
Cause of the Fault
Remedy
1
DIP switch not correctly set
Adjust according to the instructions
2
Room unit KKM2 not connected correctly
Check wiring
3
Sensor not connected correctly or defective
Measure resistance, replace where appropriate
4
Defective room unit/KKM2
Replace room unit, where appropriate
5
Short circuit in the cable to the flow
Check cable, replace where appropriate
temperature sensor S1
6
Pump does not turn, possibly seized
Check connections:
attempt to turn the shaft with a screwdriver
7
Water loss
Search for leakage and correct, refill system
9
Fan not connected correctly
Check connections
10
Fan is dirty
Clean fan (see section 8.0)
11
Fan is defective
Replace fan
12
Gas shut off valve closed
Open gas shut off valve
13
Gas pressure too low
Check gas supply cross section and gas meter
14
Defective fuse (to the left on the boiler control panel)
Replace fuse
15
Minimum or maximum adjustment at the
Regulate again (section 6)
gas multi-purpose valve not correct
16
Gas multi-purpose valve is not connected correctly
Check connections
17
Ignition cable not connected correctly
Check cables for over heating,
and security or moisture
18
Defective transformer
Replace transformer
19
Siphon is dirty/blocked
Flush siphon, and check condense
waste system is clear
21
Contact resistance at the STB water or
Measure resistance over STB,
at the STB exhaust gas too high
if resistance is over 1
Ω
, replace STB.*
22
Resistance in the air supply/exhaust gas system too high
Check length and cross section, possibly clean
23
Flue gas re-recirculation
Check exhaust connections
25
Heat exchanger is dirty
Clean
26
STB water is defective
Replace STB *
27
Incorrect or no gas injector, not mounted correctly
Check gas injector
28
Defective STB exhaust gas
Replace STB *
29
Defective control panel
Replace boiler control panel
30
Incorrect position of the ignition electrode
Carefully bend, the gap distance to the burner
must be 4 to 5mm
31
Damp
Wipe up water, possibly dry with an electric hairdryer
32
Mains connection not correct
Check and rectify
33
Wiring interrupted
Check and rectify
34
‘Reset’ button pressed too long, possibly jammed
Press ’reset’ button briefly, check whether it sticks;
if the fault does not disappear,
then replace boiler control panel
35
Earth wire not attached correctly
Press ‘reset’ button, check earth connection.
If the fault does not disappear,
then replace boiler control panel
39
Hot water primary pump does not work correctly
Check pumps, replace where appropriate
44
Fuse 24V defective
Replace fuse
45
Maintenance interval expired
Press service button for 10 seconds and
carry out maintenance/inspection.
*STB = Limit Thermostat
Summary of Contents for STRATA 3 220
Page 39: ...STRATA3 39 11 0 parts list Strata 3 220...
Page 40: ...40 STRATA3 11 0 parts list contd Strata 3 220...
Page 41: ...41 STRATA3 11 0 parts list contd Strata 3 220...
Page 42: ...42 STRATA3 11 0 parts list contd Strata 3 220...
Page 43: ...43 STRATA3 11 0 parts list contd Strata 3 330...
Page 44: ...44 STRATA3 11 0 parts list contd Strata 3 330...
Page 45: ...45 STRATA3 11 0 parts list contd Strata 3 330...
Page 46: ...46 STRATA3 11 0 parts list contd Strata 3 330...