STRATA3
9.0 fault
diagnosis
9.1 fault list
Possible faults are entered in the following tables. The right column contains the corresponding line
numbers of the error correction list – see section 9.2. The error correction list contains possible causes
as well as information about the elimination of the fault.
Fault Indication on the Display
Type of fault
Error correction list line
number – Section 9.2
(no text)
Strata 3 is turned on, ON/OFF switch does not light up,
14, 29, 31
no indication in the display.
(no text)
ON/OFF switch lights up, however, no indication in the display.
14, 29, 31
FAULT RU
Strata 3 does not receive any PWM signal
1, 2, 4, 33, 44
from the room unit or KKM2
FAULT OS
Interruption of the connection to the outside temperature sensor
1, 3, 33
IGNIT FAULT
No flame after 4 ignition attempts
12, 13, 15, 16, 17, 30, 31
FLAME OUT
Flame goes out 4 times in sequence in operation
13, 15, 17, 23, 27
STB WATER
STB water limit exceeded*
5, 6, 7, 21, 25, 26, 31
STB EXHAUST GAS
STB exhaust gas limit exceeded*
6, 7, 21, 25, 28
FAN HIGH
Controller identifies fan speed too high
9, 11, 29, 31, 33
FAN LOW
Fan speed too low
9, 10, 11, 18, 29, 31, 33, 44
FAN OP
Fan operation is identified when fan should be off
17, 30
FLAME W/O OP
Flame identified when burner should be off
17, 30
SX INTERRUPT
Connection to sensor x interrupted (S1: flow temperature sensor, 3, 33
S4: Return temperature sensor, S7: Mixer circuit sensor
GAS VALVE
Connection to the gas multi purpose valve interrupted
16, 21, 29, 31, 33
EEPROM
Fault during the checking of the EEPROM in the controller
29, 35
FAULT SOFT
Software error in the controller
29, 35
RESET BUTTON
Fault during the checking of the ‘reset’ button
29, 34, 35
LIMIT F/R
Boiler temperature too high
5, 6, 7
SERVICE
Maintenance interval expired
‘45
A3
Connection to the gas multi purpose valve interrupted
16, 21, 29, 31, 33, 35
A6
Fault during the checking of the ‘reset’ button
29, 34, 35
A7
Fault during the checking of the EEPROM in the controller
29, 35
A9
Software error in the controller
29, 35
A0, A1, A2, A4
Fault in the controller
29, 35
CO content too high
15, 27
CO
2
content too high
15, 23
CO
2
content too low
15, 27
Yellow flames
‘23
Hot water temperature too low
3, 22, 39
Output too low
’22, 15
*STB = Limit Thermostat
The following faults are visual problems and the right column contains possible error corrections as above, to eliminate these faults.
Summary of Contents for STRATA 3 220
Page 39: ...STRATA3 39 11 0 parts list Strata 3 220...
Page 40: ...40 STRATA3 11 0 parts list contd Strata 3 220...
Page 41: ...41 STRATA3 11 0 parts list contd Strata 3 220...
Page 42: ...42 STRATA3 11 0 parts list contd Strata 3 220...
Page 43: ...43 STRATA3 11 0 parts list contd Strata 3 330...
Page 44: ...44 STRATA3 11 0 parts list contd Strata 3 330...
Page 45: ...45 STRATA3 11 0 parts list contd Strata 3 330...
Page 46: ...46 STRATA3 11 0 parts list contd Strata 3 330...