19
STRATA3
5.8 Add on Modules
5.8.1 Pump module PR 01
The PR 01 pump control serves to control an additional heating circuit pump (pump 2).
Mounting
●
Remove the 4 screws on the front of the
pump control.
●
Remove the cover.
●
Mount the unit in the space provided inside the
boiler casing.
●
Refer to the instructions supplied with the unit.
140
60
115
Technical Information
●
Supply Voltage – 230V 50Hz
(mains from Strata 3 appliance)
●
Maximum contact load – 2A
●
Maximum contact rating – 120W
NOTE:
The DIP switch of the Strata 3 must be
adjusted so that only one direct heating circuit is
controlled (DIP 1 = OFF).
If the power consumption of pump 2 is more
than 120W, an auxiliary relay is to be installed.
Fig 5.7j
Fig 5.7k
Fig 5.7L
PR01
Control
Module
PR01
Control
Module