Level Two Engineer Parameters 

Description Range 

 

16 & 27 H 

(16 & 27 HS) 

 27 S 

[47 S] 

 45,75,77 H  

75 & 77 HM 

{Cascade Slave 

Boilers}      

H90 

Reduced Temperature for DHW 

8….60 

10 

10 

10 

10 

H91 

DHW Production Control  

(0=Time control 1=Constant) 

0…1 

1 0 0 

H93 

DHW Production Control 0=Non Eco 1=Eco 

0…1 

H94 

DHW Secondary Pump Control 

(0= As H91. 1= As HWS Time Switch)  

(K2, X2:03, H615:6)

 

0…1 

0 0 0 

H503 

Minimum boiler setpoint temperature  

(20 °C<=TkSmin<=TkSmax)  

20 ... 90 °C 

20 

20 

20 

20 

H504 

Maximum boiler setpoint temperature 

 

(TkSmin<=TkSmax<=90 °C)

  

20 ... 90 °C 

90 

90 

90 

90 

H505 

Boiler setpoint at design outside temperature  

20 ... 90 °C 

85 

85 

85 

85 

H506 

Minimum flow setpoint temperature  

(20 °C<=TvSmin<=TvSmax)  

20 ... 90 °C 

25 

25 

25 

25 

H507 

Maximum flow setpoint temperature  

(TvSmin<=TvSmax<=90 °C)

  

20 ... 90 °C 

90 

90 

90 

90 

H516 

Summer / winter changeover temperature  

(30 °C: S / W changeover deactivated)  

8 ... 30 °C 

18 

18 

18 

18 

H532 

Heating curve slope heating circuit 1  

1 ... 40 

32 

32 

32 

32 

H533 

Heating curve slope heating circuit 2  

1 ... 40 

H536 

Maximum speed at maximum output in heating 
mode                           

(maximum speed limitation)

  

0 ... 9950 rpm 

5000

 

5000 

[7000]

 

7000 7000 

H541 

Maximum degree of modulation in heating 
mode 

(LmodTL <= PhzMax <= LmodVL)

0 ... 100 % 

65 

65 

[100] 

100 100 

H542 

Minimum boiler output in kW  

(lower calorific value)  

0 ... 9999 kW 

[15] 

15 15 

H543 

Maximum boiler output in kW  

(lower calorific value) 

0 ... 9999 kW 

25 

25 

[75] 

75 75 

H544 

Overrun time of pumps, max. 210 min  

(setting 255: continuous operation of Q1) 

0 ... 255 min 

10 

10 

10 

10 

H545 

Minimum burner pause time  

(heat demand-dependent switching hysteresis) 

0 ... 3600 s 

300 

300 

300 

300 

H551 

Constant for quick setback without room 
influence 

0 ... 20 

H552 

Hydraulic system adjustment 

0 ... 255 

67 

70 

66 

80 

554 

Setting flags: status code open-circuit sensor 
for ANx channel suppressed / not suppressed 

0 ... 255 

b0=1 
b1=0 
b2=1 
b3=1   
b4=0   
b5=1   
b6=0   
b7=0 

b0=1 
b1=0   
b2=1 
b3=1   
b4=0   
b5=1   
b6=0   
b7=0 

b0=1   
b1=0   
b2=1  
b3=1   
b4=0   
b5=1   
b6=0   
b7=0 

b0=1   
b1=0   
b2=1  
b3=1   
b4=0   
b5=1   
b6=0   
b7=0 

 

 

Summary of Contents for ProCon Boiler Controller

Page 1: ...quired will be dependent upon the age of the appliance and the required system control All appliance operational mode adjustments and settings are undertaken via the unit control fascia Legend Button...

Page 2: ...m settings Fault Indication Boiler Flow Temperature Stored HWS Operation Mode Outside Air Temperature Legend Button Label Function 1 WATER PRESSURE INDICATOR Not used In ProCon Ranges 2 MAIN DISPLAY F...

Page 3: ...on that is available To access these parameters the following sequence must be undertaken Press and release the INFO Press Hold the Program Buttons simultaneously for at least 3 second The display wil...

Page 4: ...ode will be generated and displayed by the failing appliance and all LPB networked RVA and Opentherm units If a fault is encountered by a RVA controller or is communicated to a RVA controller via the...

Page 5: ...perating at correct speed LMU Version D E 130 Flue Temperature Too High Auto Resetting E 131 Fault With Burner E 132 External Safety Interlock Activated Open Circuit E 133 No Flame Detected After Fina...

Page 6: ...Signal Lost During Operation 99 Flame Signal Lost During Operation 100 Flame Signal Lost During Operation 101 Flame Signal Not Detected Following Last Ignition Attempt 102 Flame Signal Not Detected F...

Page 7: ...or Program Buttons The display will now indicate Use the Program Buttons to access the desired parameter line Use the Button to alter the displayed parameter to the required setting To save the adjus...

Page 8: ...ch 1 Third Off 00 00 24 00 Time Switch 2 Heating Zone 2 Set Points AGU2 500 Clip and QAD36 sensors required P20 Heating Circuit 2 Time Switch 2 Day Selection 1 2 1 5 1 7 1 7 P21 Heating Circuit 2 Time...

Page 9: ...er winter changeover temperature 30 C S W changeover deactivated 8 30 C 18 18 18 18 H532 Heating curve slope heating circuit 1 1 40 32 32 32 32 H533 Heating curve slope heating circuit 2 1 40 1 1 1 1...

Page 10: ...units 3 12 0 16 1 1 1 2 3 12 H606 LPB segment number of LMU 0 14 0 0 0 0 H614 Program input LMU basis 0 255 3 3 3 3 H615 Function programmable output K2 LMU 0 255 0 0 0 0 H618 Progr input on clip in...

Page 11: ...umber of Occurrences H713 5th Historical Fault Operating Phase H714 5th Historical Fault Operating Error Code H715 Current Historical Fault Number of Occurrences H716 Current Historical Fault Operatin...