Enhanced Fault Diagnosis Codes (LMU Internal Software Diagnostic Codes) 
 
If required a more detailed fault diagnosis code can be viewed. This will assist where a definitive 
cause for a repeated operational error cannot be found. 

The enhanced fault diagnosis code is displayed at b0 within the second INFO level.  

Access to this level can is detailed on page three of this guide.  

The table below indicates a limited number of enhanced fault codes. If the exact number indicated 
by the appliance is not detailed below please call our Technical Department or guidance. 

Fault Code 

Fault Description 

83 

Combustion Fan Not Reaching Ignition Speed 

87 

Combustion Fan Operating Beneath Minimum Setting 

90 

Combustion Fan Not Reaching Pre Purge Speed 

96 

Flame Rectification Signal Detected When Burner Off 

97 

Flame Rectification Signal Detected When Burner Off 

98 

Flame Signal Lost During Operation 

99 

Flame Signal Lost During Operation 

100 

Flame Signal Lost During Operation 

101 

Flame Signal Not Detected Following Last Ignition Attempt 

102 

Flame Signal Not Detected Following Last Ignition Attempt 

170 

The Reset Button is being Continually Depressed. (Possible Display Module Mounting Error.) 

259 

The Reset Button Has Been Pressed When No Error Has Been Displayed (E153 Generator.) 

282 

Combustion Fan Not Reaching Correct Speed 

400 

System Hydraulic Error. Return Temperature > Flow Temperature. (Repeatedly.) 

401 

System Hydraulic Error. Return Temperature > Flow Temperature. (Repeatedly.) 

402 

System Hydraulic Error. Return Temperature > Flow Temperature. (Repeatedly.) 

403 

System Hydraulic Error. Return Temperature > Flow Temperature. (Repeatedly.) 

404 

System Hydraulic Error. Return Temperature > Flow Temperature. (Repeatedly.) 

406 

Boiler Flow Temperature Rising to Above Maximum Limit Temperature When Burner Is On. 

422 

Boiler Flow Temperature Rising to Above Maximum Limit Temperature When Burner Is Off. 

433 

System Hydraulic Error. 

Δ

T between Flow and Return Too High. (Repeatedly.) 

434 

System Hydraulic Error. 

Δ

T between Flow and Return Too High. (Repeatedly.) 

435 

System Hydraulic Error. 

Δ

T between Flow and Return Too High. (Repeatedly.) 

  

 

Summary of Contents for ProCon Boiler Controller

Page 1: ...quired will be dependent upon the age of the appliance and the required system control All appliance operational mode adjustments and settings are undertaken via the unit control fascia Legend Button...

Page 2: ...m settings Fault Indication Boiler Flow Temperature Stored HWS Operation Mode Outside Air Temperature Legend Button Label Function 1 WATER PRESSURE INDICATOR Not used In ProCon Ranges 2 MAIN DISPLAY F...

Page 3: ...on that is available To access these parameters the following sequence must be undertaken Press and release the INFO Press Hold the Program Buttons simultaneously for at least 3 second The display wil...

Page 4: ...ode will be generated and displayed by the failing appliance and all LPB networked RVA and Opentherm units If a fault is encountered by a RVA controller or is communicated to a RVA controller via the...

Page 5: ...perating at correct speed LMU Version D E 130 Flue Temperature Too High Auto Resetting E 131 Fault With Burner E 132 External Safety Interlock Activated Open Circuit E 133 No Flame Detected After Fina...

Page 6: ...Signal Lost During Operation 99 Flame Signal Lost During Operation 100 Flame Signal Lost During Operation 101 Flame Signal Not Detected Following Last Ignition Attempt 102 Flame Signal Not Detected F...

Page 7: ...or Program Buttons The display will now indicate Use the Program Buttons to access the desired parameter line Use the Button to alter the displayed parameter to the required setting To save the adjus...

Page 8: ...ch 1 Third Off 00 00 24 00 Time Switch 2 Heating Zone 2 Set Points AGU2 500 Clip and QAD36 sensors required P20 Heating Circuit 2 Time Switch 2 Day Selection 1 2 1 5 1 7 1 7 P21 Heating Circuit 2 Time...

Page 9: ...er winter changeover temperature 30 C S W changeover deactivated 8 30 C 18 18 18 18 H532 Heating curve slope heating circuit 1 1 40 32 32 32 32 H533 Heating curve slope heating circuit 2 1 40 1 1 1 1...

Page 10: ...units 3 12 0 16 1 1 1 2 3 12 H606 LPB segment number of LMU 0 14 0 0 0 0 H614 Program input LMU basis 0 255 3 3 3 3 H615 Function programmable output K2 LMU 0 255 0 0 0 0 H618 Progr input on clip in...

Page 11: ...umber of Occurrences H713 5th Historical Fault Operating Phase H714 5th Historical Fault Operating Error Code H715 Current Historical Fault Number of Occurrences H716 Current Historical Fault Operatin...

Reviews: