010310 Draft
5.0 Technical Data
Technical Data
Units
ECOSTAR
515
ECOSTAR
518
ECOSTAR
522
ECOSTAR
527
Number of Sections
2
3
4
4
Nominal Heat Input Net
Max
kW
15.7
17.9
22.1
26.4
Nominal Heat Output
Max
kW
16.1
18.4
22.5
26.9
Flow and Return Connections
1.5”
1.5”
1.5”
1.5”
Flue Gas Temperature
O
C
80 80 80 80
Minimum
Water
Pressure
bar
0.5 0.5 0.5 0.5
Max
Water
Pressure
bar
3 3 3 3
Power Supply (230 V / 50 Hz)
Amps
Burner
Dependant
Burner
Dependant
Burner
Dependant
Burner
Dependant
Max Power Consumption
Watts
Burner
Dependant
Burner
Dependant
Burner
Dependant
Burner
Dependant
Limit Temperature
O
C 110 110 110 110
Maximum Flow Temperature
O
C
90 90 90 90
Water
Content
Ltrs
23 23 23 23
Minimum
Flow
Rate
Kg/S
0.55 0.63 0.79 0.96
Lift Weight (Dry)
kg
110
115
119
119