3. Operations
Setting the filename for upload:
Enter the filename of the file to be uploaded in the Filename field, and press
Apply
.
Testing the FTP upload configuration:
This test validates that the unit is able to contact and log onto the specified FTP server, download the firmware
file and verify that the firmware file is valid for this unit.
Press
Test
.
SNTP
The SNTP configuration page is used for setup and maintenance of SNTP support.
Setting the SNTP Server Address:
Enter the IP address in the primary and/or secondary address field and press
Apply
.
SNMP
The SNMP configuration page is used for setup and maintenance of all settings required to enable SNMP
support as well as access to the trap configuration pages. For additional information on SNMP support and
detailed descriptions of available traps, see on page 47.
NOTE: Traps are generated according to a hierarchical architecture; i.e. if a Tower Status enters a trap
condition, only the Tower Status trap is generated. Infeed and Outlet Status traps are suppressed until the
Tower Status returns to Normal.
Enabling or disabling SNMP support:
Select
Enabled
or
Disabled
from the drop-down menu and press
Apply
.
Setting the community strings:
Enter the community string in the appropriate field and press
Apply
.
Community strings may be 1 to 24 characters
Setting the trap timer:
Enter a trap timer value in the Error Trap Repeat Time field and press
Apply
.
The Error Trap Repeat Time value may be 1 to 65535 (in seconds).
Setting trap destinations:
Enter an IP address in the appropriate Trap Destination field and press
Apply
.
Enabling or disabling tower traps:
Click on the
Tower Traps
link.
On the subsequent Tower Traps page, select or deselect the desired traps and press
Apply
.
Configuring input feed traps:
Click on the
Input Feed Traps
link.
On the subsequent Input Feed Traps page, select or deselect the desired traps and press
Apply
.
For Load traps, enter a maximum load value for the infeed in the High Load Threshold field and press
Apply
.
The High Load Threshold value may be 0 to 255 (in amperes).
Configuring outlet traps:
Click on the
Outlet Traps
link.
On the subsequent Outlet Traps page, select or deselect the desired traps and press
Apply
.
Page 20 - 301-0399-4 Rev A.