MGE UPS SYSTEMS
Pulsar ESV 8+
Rack
/11+
Rack
/14+
Rack
/22+
Rack
: 86-153523-00
14
option 1
■
status information card: after the card is
installed in the rear of the Pulsar, communi-
cation port
15
transmits status information
on a SUB-D 9-pin female connector using
the following pinouts:
1 - ground,
4 - normal operation,
5 - common,
7 - low battery warning,
9 - operation on battery.
communication
The communication port 9 , at the rear of
Pulsar, delivers information in the form of
an RS232 serial link supported by the com-
munication protocol exclusive to
MGE UPS SYSTEMS. The Solution-Pac
programs use the data made available by
this protocol.
9
V
I
5
4
3
2
1
9
8
7
6
0V
RD TD
1 - ground
2 - TD
3 - RD
5 - common
With the ESV Driver software program you
can set up Pulsar ESV+
Rack
to suit your
user conditions (ESV Tuner). To install ESV
Driver, connect the serial cable supplied to
COM1 to COM4 (set up by ESV Tuner) seri-
al port of your computer equipped with
Windows 3.1 or 95/98 on the one end, and
to the serial Pulsar ESV+
Rack
connector
on the other end.
ESV Driver software (included in the
CD-ROM: EMB/ESVPLUS/CONFIG) lets
you edit the default parameter of Pulsar:
■
battery test frequency
(default: every week);
■
nominal output voltage
(default: 120 Volts);
■
high/low voltage thresholds
(default: 138/92 Volts);
15
n.o.
n.c.
n.o.
5
4
3
2
1
9
8
7
6
0V
0V
0V
Relay breaking capacity:
Vmax = 25V DC, Imax = 10mA
n.o. : normally open,
n.c. : normally closed.
option 2
■
SNMP card: after the card is installed in
the rear of the Pulsar, communication port
15 transmits information supported by the
TCP/IP and SNMP protocols on an RJ45
connector to any ethernet network.
Contact your sales agent for further details.
■
Fader/Booster activation thresholds
(default : 102/128 Volts);
■
on/off conditions:
■
■
automatic restart,
■
■
forced reboot,
■
■
energy saving,
■
■
cold start.