Parameters for bypass AC source and load cables for a parallel UPS
configuration
Rated unit
Number of
Total UPS
Bypass AC
Cable cross-
output
parallel-
rated output
source or load
section (1)
in kVA
connected
in kVA
line current
in mm2
units
in Amps
20
2
40
58
35
3
60
87
50
4
80
116
50
30
2
60
86
50
3
90
129
70
4
120
172
70
40
2
80
116
50
3
120
174
70
4
160
232
120
50
2
100
144
70
3
150
216
95
4
200
288
150
60
2
120
174
70
3
180
261
120
4
240
348
185
80
2
160
232
120
3
240
348
185
4
320
464
2x95
100
2
200
288
150
3
300
432
185
4
400
576
2x120
120
2
240
348
185
3
360
522
2x120
4
480
696
2x150
160
2
320
462
2x95
3
480
693
2x150
4
640
924
3x120
200
2
400
578
2x120
3
600
866
2x185
4
800
1155
3x185
(1) cable cross-sections are given for copper
conductors of the U1000 R02V type (increase by
30% for aluminium conductors). They are
calculated according to permissible temperature
rise and allow for line voltage drops over a
The table opposite serves as an
example for a parallel-connected
installation comprising up to four UPS
units.
◗
for installations with redundant units,
take into account only the units
required to supply the load power (e.g.
for an installation made up of 3 parallel-
connected UPS units, one being
redundant, only 2 UPS units are used
to determine bypass AC source and
load currents and cable cross-
sections);
◗
this table has been drawn up for
rated phase-to-phase bypass AC
source and load voltages of 400 V and
full rated load with a power factor of
0.8. For voltages of 380 V or 415 V,
multiply the indicated currents by 1.05
and 0.96 respectively, then modify the
cable cross-sections accordingly, if
necessary.
The cable cross-sections in this table
concern the parts illustrated in bold in
the simplified diagram in figure 3,
where:
1: normal AC source,
2: bypass AC source,
A: external bypass.
maximum length of 100 m. For greater lengths, the
cross-sections should be chosen to limit voltage
drops to 3%.