E-51028231XU/BH
- 15
Battery cubicle
See figure 15.
The battery cubicle shown is an
example only, given that characteristics
of these cubicles vary greatly from one
cubicle to another.
◗
remove the cardboard covers and all
the hooping (used only for transport);
◗
remove the terminal shield from the
battery circuit breaker "QF1" to make
the connections to this circuit breaker;
◗
in the case of installations having
several battery cubicles, the
connections to be made between
cubicles are indicated in the
instructions accompanying the cubicles
(or in the drawing file for complicated
installations);
◗
in the case of a UPS with a power
rating from 80 to 120 kVA and
connection via the top, the battery
cubicle containing circuit-breaker QF1
cannot be connected to the UPS
cubicle via the bottom. A roof equipped
with a cable gland can be installed on
this battery cubicle in order to connect it
directly via the top to the inverter
cubicle. Please contact our after-sales
service.
Important:
◗
the cubicle is supplied with a fixture
locking circuit breaker "QF1"in the open
position. Do not remove this fixture
before commissioning. Accidental
closing of "QF1" will power up the
downstream circuits which could be
hazardous for personnel and
permanently damage the battery by
deep discharge;
◗
connections between battery cubicles
should be made in compliance with
applicable regulations. Take all
protective measures associated with
working on live equipment and in
particular use only qualified personnel
equipped with gloves, protective
goggles, insulated tools, etc.
Cables are connected to copper
terminals by lugs.
Note:
The optional "Temperature Monitor"
unit is located at the top in one of the
battery cubicles. The cubicles not fitted
with a battery circuit breaker include an
additional shelf for battery cells.
Key to figure 15:
AA: cross-sectional view of the cubicle,
B: front view of the cubicle,
C: front panel,
D: rear panel,
E: cable ties to duckboard shelf,
F: cable exit through the bottom,
G: trough, if applicable,
H: connection of exposed conductive
parts to duckboard shelf,
I:
cable exit to battery connection
point in UPS cubicle,
J: cable exit to an additional battery
cubicle, if applicable,
K: cable ties to duckboard shelf,
L: fixture locking circuit breaker "QF1"
in the open position.
Fig. 15
XR1
QF1
+
+
D
C
A
A
L
K
I
J
F
G
E
H
B
AA
Installation
(cont.)
(qualified personnel only)
Summary of Contents for GALAXY PW 100 kVA
Page 2: ...2 E 51028231XU BH...
Page 30: ...30 E 51028231XU BH...