3. Connection

3.1 Connection points

  

3.2 Connection diagrams

  

Cabinet for Galaxy 5000 of 20 kVA to 160 
kVA 

(with battery backup time < or = to 10 

mn)

, and of 20 kVA to 100 kVA 

(with battery 

backup time > 10 mn)

:

  connection to the inverter on 25 x 5 mm 

copper terminals with 8.2 mm diameter 
holes,

  connection to the battery on 25 x 5 mm 

copper terminals with 8.2 mm diameter 
holes,

  earth connection on 8 mm diameter 

threaded rod, or on 50 x 5 mm copper 
terminal.

Cabinet for Galaxy 5000 of 100 kVA to 120 
kVA 

(with battery backup time > 10 mn)

:

  connection to the inverter on 32 x 8 mm 

copper terminals with 12.2 mm diameter 
holes,

  connection to the battery on 32 x 10 mm 

copper terminals with 12.2 mm diameter 
holes,

  earth connection on 8 mm diameter 

threaded rod, or on 50 x 5 mm copper 
terminal.

Connection for a type 1 cabinet without insulation monitor 

(see electrical characteristics table)

  the cross-section of the power cables is 

given in the tables in the section entitled 
"characteristics of cabinet",

  recommended cross-section of auxiliary 

conductors: 1 mm2 (terminal acceptance 
capacity: 2.5 mm2),

  make sure that the auxiliary conductors and 

power cables do not follow the same path,

  power cables and auxiliary conductors are 

not supplied.

Important

: leave the QF1 circuit-breaker in 

"off" position until the 

Galaxy 5000 

unit has 

been commissioned.

QF1

L-

L+

B+

XR1 XR2

A

A

B-

to battery

auxiliaries

to inverter

cubicle

L-

L+

1 2

3

4

11

14 D1

D4

B-

B+

to battery

position

contact of

QF1 circuit-

breaker

QF1 tripping:

24V under

voltage coil

to inverter

QF1 battery

circuit-breaker

XR1

terminal

block

battery

circuit-

breaker

cabinet

XMB 08   XMB 07   XMS 06

Galaxy 5000

Summary of Contents for Galaxy 5000

Page 1: ...34003641FR AA Page 1 T H E U N I N T E R R U P T I B L E P O W E R P R O V I D E R www mgeups com Galaxy 5000 20 120 kVA Battery circuit breaker cabinet Installation manual...

Page 2: ...esign approach used in product development the elimination of harmonic disturbances reinjected into the AC source production in an ISO 14001 certified factory recycling of the Galaxy 5000 at the end o...

Page 3: ...or horizontal position the cabinet door is closed by two lock knobs with a key 405 type on one of the knobs see fig 1 the cabinet version with insulation controller has the same characteristics as the...

Page 4: ...550 15 600 400 200 658 350 458 550 17 35 30 600 400 200 658 350 458 550 15 600 400 200 658 350 458 550 17 35 40 600 400 200 658 350 458 550 15 600 400 200 658 350 458 550 17 35 60 600 400 200 658 350...

Page 5: ...lease Magnetic setting Thermal setting 20 or to 10 mn NS100 TM100D 800 A 1 10 mn NS100 TM100D 800 A 1 30 or to 10 mn NS100 TM100D 800 A 1 10 mn NS100 TM100D 800 A 1 40 or to 10 mn NS100 TM100D 800 A 1...

Page 6: ...ection on 8 mm diameter threaded rod or on 50 x 5 mm copper terminal Connection for a type 1 cabinet without insulation monitor see electrical characteristics table the cross section of the power cabl...

Page 7: ...TR5A KA1 1 L B B XMB 08 XMB 07 XMS 06 power supply unit insulation fault to the insulation circuit breaker of AC normal source in the Galaxy 5000 cubicle see figure on next page Galaxy 5000 to batter...

Page 8: ...34002025EN AA Page 8 3 Connection XB3 XB3B XB2 XB2B XB1 XB1B XB4 XB4B To terminals 1 2 3 4 of QF1 circuit breaker To terminals 1 2 of cabinet Insulation circuit breaker To insulation circuit breaker...