2. Installation

PowerServices TelPac external unit (2 4 extensions)

Four similar inputs C, D, E, F are available
inside the external unit on terminal block
XM13.
To connect contacts to these four inputs,
proceed as follows:

 Remove the cover (partly unscrew the

screws and pivot the cover).

 Remove the card from the external unit (3

screws).

 Feed the cable through the grommet.

 Connect the cable(s) to terminal block

XM13 as shown in the figure opposite.

 Replace the card in the external unit and fix

it in place (3 screws).

 Replace the cover.

PowerServices TelPac

 is now ready for the

parameter setting stage required for
Teleservice. Consult the Technical Support
documentation. Lastly, move on to step 2
(see section 2.1 "Procedure").

Extension

C

D

E

F

Settings

JBUS / RS485

PowerServices TelPac

UPS

CD

Phone

A 5V B R+ R- T+ T-

A

B

5V

< 10m

Terminal block
XM13

All manuals and user guides at all-guides.com

Summary of Contents for 66096

Page 1: ...UPS SYSTEMS T H E U N I N T E R R U P T I B L E P O W E R P R O V I D E R Settings JBUS RS485 PowerServices TelPac UPS CD Phone A 5V B R R T T Settings JBUS RS485 PowerServices TelPac UPS CD Phone A...

Page 2: ...Page 2 34003602EN AB All manuals and user guides at all guides com...

Page 3: ...Environment MGE UPS SYSTEMS pays great attention to the environmental impact of its products during the design and manufacture stages and through to the end of its life cycle MGE UPS SYSTEMS products...

Page 4: ...and manufacturer s instructions Federal Communication Commission FCC statement Part 15 This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to part...

Page 5: ...tralia Austria Belgium Brazil Bulgaria Canada China Czechoslovakia Denmark Finland France Germany Greece Hong Kong Hungary India Ireland Israel Italy Japan Korea Luxembourg Malaysia Mexico New Zealand...

Page 6: ...that must always be followed Pictogram symbols UPS Uninterruptible Power System The conventions used to represent indicator lights in the illustrations are as follows Indicator off Indicator on Flashi...

Page 7: ...tting up the RS485 link 18 General 18 Single unit type installation 18 Impedance matching and bias settings 19 Configuring the shielding terminal 20 Configuring the RS485 card for Comet 21 Configuring...

Page 8: ...8 34003602EN AB Contents 3 Maintenance 3 1 Cable diagrams 30 Serial cable diagrams ref 34003618 30 Modem cable ref 34003729 30 Comet link cable ref 34003747 30 All manuals and user guides at all guide...

Page 9: ...telephone line ATTENTION Onduleur sous Teleservice WARNING UPS under Teleservice MGE UPS SYSTEMS Ne pas mettre hors tension sans avoir au pr alable arr t la ligne t l phonique Do not switch off witho...

Page 10: ...puts Shielding configuration jumper RS232 serial port for configuration or maintenance Card name RS485 terminal block for connection of MGE UPS SYSTEMS equipment Connection port for 2 contact inputs A...

Page 11: ...by MGE UPS SYSTEMS is possible via a dry contact connection The card version is designed for insertion in a UPS with a specific communication card slot The external version is designed for installati...

Page 12: ...ity Line protection included Normally open NO 0 08 0 6 mm2 28 20 AWG 2 card version 2 4 external version 0 08 0 5 mm2 28 20 AWG 10m maximum 5V DC 1A Parameters Rate Data bits Stop bits Parity Rate bit...

Page 13: ...a with UPS Modem connected Modem not connected Communication with all remotely monitored UPSs OK Communication with at least one of the remotely monitored UPSs NOK Modem connected Modem not connected...

Page 14: ...igger remote monitoring of your equipment 2 2 Preliminary check Before starting the installation Make sure that an analogue type telephone outlet with an RJ11 jack is available in the vicinity of the...

Page 15: ...sales 1 Galaxy must be equipped with at least one JBUS RS485 communication card with a free port COM2 2 Comet S31 must be equipped with one JBUS RS485 communication card A protected and UPS secured o...

Page 16: ...ervice centre 2 5 Fitting the warning label A set of yellow warning labels is provided in the PowerServices TelPac kit This label is designed to warn MGE UPS SYSTEMS field technicians that the equipme...

Page 17: ...et EXtreme Comet S31 fault ATTENTION Onduleur sous Teleservice WARNING UPS under Teleservice MGE UPS SYSTEMS Ne pas mettre hors tension sans avoir au pr alable d connect la ligne t l phonique Do not s...

Page 18: ...one point The external unit is pre configured to be directly operational No special configuration is necessary for a Single unit type installation of the external unit with a Galaxy or Comet type UPS...

Page 19: ...n T to R connection T 0V bias R R impedance matching Switch number 5 6 7 8 Function R 0V bias T 5V bias T T impedance matching R 5V bias Default position Master fixed Two wire link Bias Without impeda...

Page 20: ...ctrical measurements are to be made on the RS485 link it is possible to configure the shielding terminal of terminal block 7 as a 0V terminal The holes above each terminal allow a measurement probe to...

Page 21: ...h the recommended configuration see section Single unit type installation They must be made before installing and commissioning the PowerServices TelPac external unit The slave number is set to 1 by d...

Page 22: ...ices TelPac external unit The serial link format and the slave number should be set using UPS Tuner or Soft Tunor O P N M K L J H I G A B COM2 COM1 OUVERT FERME RAUZ 6739856 O P N M K L J Also check t...

Page 23: ...tor lights see section 1 5 Indicator lights Check the status of the UPS indicator light 10 on steady for 5s status 1 in the table then regular flashing every second during the start up phase status 3...

Page 24: ...it see figures Remove the protective adhesive under the external unit Place the external unit as shown according to the type of UPS Press down hard for 10 seconds to fix the adhesive Configure the JBU...

Page 25: ...for 5s status 1 in the table then regular flashing every second status 3 in the table Check the status of CD indicator light 9 off for 5s then regular flashing status 3 in the table PowerServices TelP...

Page 26: ...t install then fix link cable 21 Bring the other end of the cable out through the grommet in panel A 7 Replace the protective panels 2 9 Installing the PowerServices TelPac external unit for Galaxy UP...

Page 27: ...y cord 20 to the back of the external unit 5V DC 13 Connect the one end of the telephone cable 22 to the phone port on the external unit and the other end to the telephone outlet If the wall outlet is...

Page 28: ...connection cable is not supplied 7 UPS Checking the indicator lights see section 1 5 Indicator lights Put the UPS back into operation Check the status of the green UPS indicator light 10 on steady fo...

Page 29: ...rews Feed the cable through the grommet Connect the cable s to terminal block XM13 as shown in the figure opposite Replace the card in the external unit and fix it in place 3 screws Replace the cover...

Page 30: ...or DB9 RJ9 cable 2 5 m RJ9 male connector 4 1 DB9 female connector RJ9 male connector 2 3 4 5 6 7 8 4 3 2 1 9 1 RJ45 male connector RJ45 RJ11 cable 5 m RJ11 male connector 8 1 6 1 RJ45 male connector...

Reviews: