2. Installation
2.7 Installing the PowerServices TelPac card
N.B.
: For
Galaxy PW
UPS
s, first attach the cover plate provided in
the pack.
Installation
(Illustrations show the
Pulsar EX
treme
UPS
)
It is not necessary to shut down the
UPS
.
◗
Unscrew and remove the cover plate of one of the free
communication card slots in the
UPS
.
◗
Insert the card and secure it using the screws.
Check the indicator lights
(see section 1.5 "Indicator lights")
◗
Check the status of the UPS indicator light
10
:
- on steady for 5s (status 1 in the table),
- then regular flashing every second during the start-up phase
(status 3 in the table),
- lastly, random flashing during data exchange with the
UPS
(status
4 in the table).
◗
Check the status of the CD indicator light
9
:
- off for 5s,
- then flashing during the start-up phase (status 3 in the table),
- lastly, off (status 2 in the table).
Connection
◗
Connect the telephone cable to the card’s phone port on one end
and the telephone outlet on the other. If the wall outlet is not
compatible with the connector proposed on the cable, use an
adapter.
Installation is now complete.
PowerServices TelPac
is operational.
Move on to stage 2 (see section 2.1 "Procedure").