47
Configuration
6.3.3 Single Stage with Enhanced Trouble Reporting Addressing
To configure the recommended base address
To configure the INX for Single Stage with Enhanced Trouble Reporting in a Mircom
System
To configure the INX for Single Stage with Enhanced Trouble Reporting in a Secutron
System
Set DIP switch SW1 as:
0-1-0-1-1-0-1-0
OFF-ON-OFF-ON-ON-OFF-ON-OFF
Set DIP switch SW2-1 to SW2-4 as:
0-0-0-1
OFF-OFF-OFF-ON
Set DIP switch SW2-1 to SW2-4 as:
0-1-0-1
OFF-ON-OFF-ON
Attention: If NACs are configured the Evacuation Rate must be set on SW2 4-6. For
more information see Setting Alert Rates, Evacuation Rates, NAC 5
Output Functions on page 42.
Table 11 Configuring Single Stage with Enhanced Reporting Functions
Function
Address
Recommended
Device Address
Common Trouble
Base Address
90
Signal Silence
Base A 1
91
Monitor AC trouble
Base A 2
92
Monitor Battery/Charger trouble
Base A 3
93
Monitor Earth Ground Fault
Base A 4
94
Activate NAC1, return NAC1 line status
Base A 5
95
Activate NAC2, return NAC2 line status
Base A 6
96
Activate NAC3, return NAC3 line status
Base A 7
97
Activate NAC4, return NAC4 line status
Base A 8
98
Activate NAC5, return NAC5 line status
Base A 9
99
SW1
1
8
2 3 4 5 6 7
SW2
ON
1
8
2 3 4 5 6 7
SW2
ON
1
8
2 3 4 5 6 7
!