Wiring
7.2.8 Relay Contact Activation from FACP - Single Stage
Figure 48 Relay Contact Activation from FACP - Single Stage
Attention: DO NOT USE AN SLC LOOP IN THIS APPLICATION.
Disable the addressable loop by setting DIP switch SW1 to all 0 (OFF).
Table 22 Difference between features provided by SLC Interface and Contact Interface
Feature Description
SLC Interface
Contact Interface
All Call
N/A
N/A
NAC by NAC activation
Yes
No
NAC circuit trouble reporting
Yes
No
Common trouble reporting
Yes
Yes
Enhanced trouble reporting
Yes
No
RELAY CONTACT ACTIVATION FROM FACP - SINGLE STAGE
-
+ + --
SYNCH INPUT1
1
8
1
8
1
8
1
8
1
8
POWER ON
ADD. LINE
ACTIVITY/
ALARM
COMMON
TROUBLE
CPU FAIL
BATTERY/
CHARGER
TROUBLE
JW1
P
P3
P4
P1
P2
AUX OUTPUT TROUBLE
SYNCH. OUT TROUBLE
GFAULT
JW2
MAIN DISPLAY PANEL
ACK.
BUTTON
FACP
Alarm
Relay
COM
NO
NC
+
-
Aux
Power
TROUBLE RELAY
NO
NC
C
P
To FACP input
configured for
trouble
!
Summary of Contents for INX-10A Series