mFi Mason-Lite MGFPST-43A Instructions Manual Download Page 19

17

apply to vents at 12” diameter or less and require a minimum 

height in accordance with the roof pitch and a minimum of 8 ft. 

distance from a vertical wall or obstruction (see Fig. 29).

Figure 29

TABLE I

Roof Pitch

Minimum Height

Feet

Meters

Flat to 7/12

1

0.3

7/12 to 8/12 

1.5

0.46

8/12 to 9/12

2

0.61

9/12 to 10/12

2.5

0.76

10/12 to 11/12

3.25

0.99

11/12 to 12/12

4

1.22

12/12 to 14/12

5

1.52

14/12 to 16/12

6

1.83

16/12 to 18/12

7

2.13

18/12 to 20/12

7.5

2.29

20/12 to 21/12

8

2.44

If venting horizontally through a side wall becomes necessary, 

a  listed  thimble  approved  for  use  with  B-type  vent  must  be 

used. Check with your local codes before venting through a 

side wall.

 

Some  codes  areas  allow  the  use  of  existing  B-type 

vent systems if the system is at or above the recommended 

diameter of the flue. The flue connection must be made using 

listed B-type connectors and the existing system must be code 

inspected for damage and proper installation.

 

It is not recommended that this appliance be common 

vented  with  an  existing  gas  burning  appliance.  However,  if 

it  becomes  necessary  to  common  vent  this  appliance,  the 

venting system must be sized and configured in accordance 

with  the  common  venting  guides Appendix  G  of  the  current 

National Fuel Gas Code NFPA No. 54/ANSI Z223.1.

Note:  Before  connecting  this  appliance  to  an  existing  vent  

system or a common venting system, consult with your local 

architect, planner, or building official.

Specifying Chimney Heights

 

If  the  horizontal  distance  from  the  mid-point  of  the 

chimney to the peak of the roof ridge is less than 10 feet, the 

top of the chimney must be at least 2 feet above the roof ridge. 

This is called the “2 foot in 10 foot” rule.

 

If  the  horizontal  distance  from  the  chimney’s  center 

measured across to the ridge of the roof is more than 10 feet, 

the top of the chimney still needs to be at least 2 feet above a 

point measured from a distance of 10 feet horizontally along 

the roof.

 

Though  there  are  many  configurations  in  meeting 

these requirements, chimney height cannot be less than 3 feet 

above the roof at the edge of the chimney.

 

If the roof is flat, the chimney must extend no less than 

3 feet from where it intersects the roof.

 

If the chimney is entering the roof at an angle, measure 

the shorter angle where the chimney intersects the roof which 

should also be at least 3 feet.

Note: The previous guidelines do not take into consideration     

outside conditions which may require a higher chimney due to 

foliage,  other  buildings,  power  lines  and  weather  conditions 

in your area. Follow the chimney manufacturer’s installation 

guide for further information.

Chimney Termination Units

 

You will be installing at or possibly near the top of the 

chimney chase flashing. A top termination unit is the essential 

piece of equipment in keeping sparks out of the atmosphere. 

Before  installing  this  important  piece  of  equipment,  you 

will  have  to  make  a  judgment  call  as  to  whether  or  not  the 

termination unit – like all the other exterior exposed chimney 

components, for that matter – should be painted in order to 

protect it/them from rusting and weathering. Particularly if you 

are installing the fireplace and chimney near water or in a high 

humidity  area,  the  manufacturer  recommends  a  top  quality, 

rust-proof  paint  especially  formulated  for  metal.  Follow  the 

paint manufacturer’s directions, applying the paint well before 

you are scheduled to install the round top termination unit or 

any of the flashings or flues that will be exposed to outside 

weather conditions.

 

Venting terminals shall not be recessed into walls or 

siding.  This  appliance,  when  installed,  must  be  electrically 

grounded in accordance with local codes and in the absence 

of local codes, with the National Electrical Code, ANSI NFPA 

70, or the Canadian Electrical Code, CSA C22.1.

Summary of Contents for Mason-Lite MGFPST-43A

Page 1: ...requirements of the ANSI Z21 50 standard Solid fuels shall not be burned in this fireplace This appliance must be vented vertically through the roof This appliance is not for installation in manufactu...

Page 2: ...This page has been left intentionally blank...

Page 3: ...20 500 mm HEARTH EXTENSION BEYOND SIDES 12 300 mm INSULATION FROM FIREBOX 0 0 mm The installation including provisions for combustion ventilation air and required minimum permanent vent opening must...

Page 4: ...NT 2 8 LOWER DOME FRONT 2 9 LOWER DOME SIDE 2 10 UPPER DOME FRONT 2 11 UPPER DOME SIDE 2 12 DOME TOP FOR 12 B VENT 1 13 INSULATION BLANKET NOT INCLUDED 14 12 VENT PLATE ASSEMBLY NOT INCLUDED 15 3 REBA...

Page 5: ...log 30 2 11 MFP 214 Burner Grate Brackets 2 2 Before beginning installation be sure the burner system is complete by comparing its contents with this Parts List Parts may differ depending upon the siz...

Page 6: ...lt in property damage or personal injury 2 3 8 SPILL SWITCH BAFFLE 43 1 4 53 29 5 8 62 1 8 A A GAS INLET 10 1 4 9 3 4 4 1 4 CHIMNEY OR UL 103 12 ID CLASS A SECTION A A CONNECT TO A 12 B VENT B 38 1 4...

Page 7: ...he gas fireplace and its required individual shut off valve must be disconnected from the gas supply piping system while performing any tests of the piping system at pressures in excess of psig The ga...

Page 8: ...plied Model No GML 2 39 44 P A WARNING Any application other than the Intended Use as stated above is in violation of the manufacturer s instructions and is hereby prohibited Such violation may cause...

Page 9: ...radiant heat is maintained to safe limits Combustible Floor Clearances MGFPST43 Mason Lite Fireplaces have been designed with zero clearance to combustible floors Mason Lite Fireplace Chimney System...

Page 10: ...Figure 11 for support of anchor rods by the steel support frames For fireplace support foundations installed on concrete refer to Appendix I and II pages 20 21 for specific instructions Rebar locatio...

Page 11: ...is the task and responsibility of the general contractor installer to see that the proper reinforcement for weight loads are made by a licensed design professional prior to the fireplace installation...

Page 12: ...quately affix all the fireplace components The mortar is premixed and dry and is to be used to adhere all the fireplace components Be sure to use clean water and work it up into a mixture that is past...

Page 13: ...e bottle brush prior to placing the epoxy This will ensure a sufficient bond to the concrete Figure 12 Note A DEPUTY INSPECTOR MAY ME REQUIRED FOR THE EPOXY DOWELS PROCESS CHECK WITH YOUR LOCAL BUILDI...

Page 14: ...till wet 7 Set the remaining lintel as shown in Figure 16 Figure 16 Lintel Lower Dome Side 8 Now you are ready to start the smoke dome assembly Take the lower side dome positioned so that the beveled...

Page 15: ...the framework to house the chimney system Now that you have completed the smoke dome assembly all the components should stack up for a smooth transition into the flue components Setting the smoke dom...

Page 16: ...he finished firebrick floor of the fireplace so that it is at least 11 eleven inches above the combustible floor system Disclaimer Masonry Fireplace Industries wishes to express that as the manufactur...

Page 17: ...hazard MFI cannot be responsible for the make up of material on the exterior of the fireplace you have chosen nor can MFI be held responsible for the materials in a room that may be responding negativ...

Page 18: ...e sections of vertical pipe that are more than 10 ten feet measuring between elbows you must insert at midpoint a chimney stabilizer When installing the stabilizer pull out the support straps with a g...

Page 19: ...n 10 feet the top of the chimney still needs to be at least 2 feet above a point measured from a distance of 10 feet horizontally along the roof Though there are many configurations in meeting these r...

Page 20: ...ht side of the baffle with the sheet metal screws so that the edges are flush with the firebrick Important This baffle assembly and only this the supplied assembly with spill switch must be properly i...

Page 21: ...and all flames main burner and pilot will go out see important note below OPERATING THE BURNER USING THE REMOTE Move the wall switch to the REMOTE position and follow the instructions included in the...

Page 22: ...nd chimney system must be completely dry This means that the unit must stand without any firing for a minimum of 28 days Only after that period of time can a first lighting take place Do not let the f...

Page 23: ...done twice a year In colder climates cleaning should be done more often Always allow the fireplace to completely cool before you work on it which means of course shutting off all gas and electrical c...

Page 24: ...lts a Check with a millivolt meter Should be 250 millivolts or more b Pilot flame making a blowing sound b Pilot needs adjusting see Checking and Adjusting the Pilot on page 22 c Generator wire leads...

Page 25: ...ncrete slab The concrete strength and durability shall comply with Sections 1903 1904 and 1905 of the International Building Code IBC TABLE R402 2 MINIMUM SPECIFIED COMPRESSIVE STRENGTH OF CONCRETE MI...

Page 26: ...ly b Lines defining areas are approximate only Local conditions may be more or less severe than indicated by region classification A severe classification is where weather conditions result in signifi...

Page 27: ...liate thereof liable in any respect for any injury or damage to the building or structure in which the fireplace has been installed or to the persons or property therein arising out of the use misuse...

Reviews: