mFi Mason-Lite MGFPST-43A Instructions Manual Download Page 18

16

MASON-LITE Chimney Systems:

This MGFPST43(P)A Mason-Lite Fireplace requires the 

installation of a Vent Plate Assembly which allows connection 

to either a 12 inch diameter B-Vent system or UL 103-12 

Class A Chimney system.

Installers are cautioned to put the chimney system together 

exactly  as  instructed  and  shown  in  chimney  manufacturer’s 

guide.  Any  variations  may  have  serious  consequences 

resulting in an accident or malfunction. If instructions are not 

followed,  the  warranty  on  the  product  will  become  null  and 

void.

Note  that  although  the  fireplace  itself  is  a  “zero  clearance” 

fireplace,  the  most  important  aspect  of  the  installation  is 

maintaining the minimum required clearances to combustible 

materials for the flue system according to the chimney pipe 

manufacturer’s  recommendations,  otherwise  a  potential  fire 

hazard may occur.

Warning:  do  not  interchange  chimney  manufacturer’s  parts 

with  any  other  parts  except  those  specifically  required  by 

the  chimney  manufacturer’s  recommendations  otherwise  a 

potential hazardous condition may be created.

A “B-type” venting system must be connected to the appliance 

for  venting  to  outside  of  building.  The  following  section  is 

provided as a guide to a standard B-type vent installation.

Standing  codes  requirements  concerning  B-type  vent 

installations  may  vary  within  your  state,  province  or  local 

codes  jurisdiction.  Therefore,  it  is  recommended  that  you 

check with your local building codes for specific requirements 

or in absence of local codes, follow Section 7.0 of the current 

National Fuel Gas Code ANSI Z223.1/NFPA 54 for Category I 

systems using double wall B-1 vent pipe.

 

This  gas  appliance  must  be  vented  to  the  outdoors 

only and may not be terminated into an attic space or into a 

chimney flue servicing a solid fuel burning appliance.

Assuming you have sections of vertical pipe that are more than 

10’ (ten feet) measuring between elbows, you must insert – at 

midpoint – a chimney stabilizer. When installing the stabilizer, 

pull out the support straps with a good amount of tension and 

hammer to the frame.

This  appliance  may  be  vented  through  a  manufactured 

chimney system or a masonry chimney using a B-vent adapter 

or a chimney liner system if the system is listed, inspected and 

approved by local codes and/or building authorities. 

The  examples  shown  in  Fig.28  are  typical  of  most  B-vent 

installations and codes practices.

Example 1:

Shows the minimum allowable system height and lateral offset 

for an inclination of 60° or greater. Code specifies that offsets 

of 60° or greater are considered horizontal and must follow 

the 75% rule for lateral to total vertical system height. Codes 

also allow only one offset in the total system when at 60° or 

greater. The total vertical height in this example represents the 

minimum height of 8 ft. and therefore the allowable lateral is 6 

ft. when the 75% rule applies. If the lateral length must exceed 

75% then the system must be sized in accordance with the 

Category I venting tables.

Example 2:

Shows  a  multiple  offset  each  at  a  45°  inclination.  Multiple 

offsets are permitted if they do not exceed a 45° inclination. 

The total lengths of the two offsets are not required to meet 

the 75% allowable rule.

Example 3:

Shows a single offset at 45° of inclination and therefore the 

lateral length at 10 ft. of offset does not have to meet the 75% 

rule. In each case the offsets must be supported and firestops 

must be positioned wherever the vent must pass through a 

sub-floor, ceiling joist or an attic overhang. The vent pipe must 

terminate vertically into a listed type vent cap and extend a 

sufficient height through an approved roof flashing, roof jack 

or a roof thimble. At all points the listed clearances must be 

maintained. Vent terminations must be located in accordance 

with height and proximity rules of NFPA No. 54. These rules 

Figure 28

Summary of Contents for Mason-Lite MGFPST-43A

Page 1: ...requirements of the ANSI Z21 50 standard Solid fuels shall not be burned in this fireplace This appliance must be vented vertically through the roof This appliance is not for installation in manufactu...

Page 2: ...This page has been left intentionally blank...

Page 3: ...20 500 mm HEARTH EXTENSION BEYOND SIDES 12 300 mm INSULATION FROM FIREBOX 0 0 mm The installation including provisions for combustion ventilation air and required minimum permanent vent opening must...

Page 4: ...NT 2 8 LOWER DOME FRONT 2 9 LOWER DOME SIDE 2 10 UPPER DOME FRONT 2 11 UPPER DOME SIDE 2 12 DOME TOP FOR 12 B VENT 1 13 INSULATION BLANKET NOT INCLUDED 14 12 VENT PLATE ASSEMBLY NOT INCLUDED 15 3 REBA...

Page 5: ...log 30 2 11 MFP 214 Burner Grate Brackets 2 2 Before beginning installation be sure the burner system is complete by comparing its contents with this Parts List Parts may differ depending upon the siz...

Page 6: ...lt in property damage or personal injury 2 3 8 SPILL SWITCH BAFFLE 43 1 4 53 29 5 8 62 1 8 A A GAS INLET 10 1 4 9 3 4 4 1 4 CHIMNEY OR UL 103 12 ID CLASS A SECTION A A CONNECT TO A 12 B VENT B 38 1 4...

Page 7: ...he gas fireplace and its required individual shut off valve must be disconnected from the gas supply piping system while performing any tests of the piping system at pressures in excess of psig The ga...

Page 8: ...plied Model No GML 2 39 44 P A WARNING Any application other than the Intended Use as stated above is in violation of the manufacturer s instructions and is hereby prohibited Such violation may cause...

Page 9: ...radiant heat is maintained to safe limits Combustible Floor Clearances MGFPST43 Mason Lite Fireplaces have been designed with zero clearance to combustible floors Mason Lite Fireplace Chimney System...

Page 10: ...Figure 11 for support of anchor rods by the steel support frames For fireplace support foundations installed on concrete refer to Appendix I and II pages 20 21 for specific instructions Rebar locatio...

Page 11: ...is the task and responsibility of the general contractor installer to see that the proper reinforcement for weight loads are made by a licensed design professional prior to the fireplace installation...

Page 12: ...quately affix all the fireplace components The mortar is premixed and dry and is to be used to adhere all the fireplace components Be sure to use clean water and work it up into a mixture that is past...

Page 13: ...e bottle brush prior to placing the epoxy This will ensure a sufficient bond to the concrete Figure 12 Note A DEPUTY INSPECTOR MAY ME REQUIRED FOR THE EPOXY DOWELS PROCESS CHECK WITH YOUR LOCAL BUILDI...

Page 14: ...till wet 7 Set the remaining lintel as shown in Figure 16 Figure 16 Lintel Lower Dome Side 8 Now you are ready to start the smoke dome assembly Take the lower side dome positioned so that the beveled...

Page 15: ...the framework to house the chimney system Now that you have completed the smoke dome assembly all the components should stack up for a smooth transition into the flue components Setting the smoke dom...

Page 16: ...he finished firebrick floor of the fireplace so that it is at least 11 eleven inches above the combustible floor system Disclaimer Masonry Fireplace Industries wishes to express that as the manufactur...

Page 17: ...hazard MFI cannot be responsible for the make up of material on the exterior of the fireplace you have chosen nor can MFI be held responsible for the materials in a room that may be responding negativ...

Page 18: ...e sections of vertical pipe that are more than 10 ten feet measuring between elbows you must insert at midpoint a chimney stabilizer When installing the stabilizer pull out the support straps with a g...

Page 19: ...n 10 feet the top of the chimney still needs to be at least 2 feet above a point measured from a distance of 10 feet horizontally along the roof Though there are many configurations in meeting these r...

Page 20: ...ht side of the baffle with the sheet metal screws so that the edges are flush with the firebrick Important This baffle assembly and only this the supplied assembly with spill switch must be properly i...

Page 21: ...and all flames main burner and pilot will go out see important note below OPERATING THE BURNER USING THE REMOTE Move the wall switch to the REMOTE position and follow the instructions included in the...

Page 22: ...nd chimney system must be completely dry This means that the unit must stand without any firing for a minimum of 28 days Only after that period of time can a first lighting take place Do not let the f...

Page 23: ...done twice a year In colder climates cleaning should be done more often Always allow the fireplace to completely cool before you work on it which means of course shutting off all gas and electrical c...

Page 24: ...lts a Check with a millivolt meter Should be 250 millivolts or more b Pilot flame making a blowing sound b Pilot needs adjusting see Checking and Adjusting the Pilot on page 22 c Generator wire leads...

Page 25: ...ncrete slab The concrete strength and durability shall comply with Sections 1903 1904 and 1905 of the International Building Code IBC TABLE R402 2 MINIMUM SPECIFIED COMPRESSIVE STRENGTH OF CONCRETE MI...

Page 26: ...ly b Lines defining areas are approximate only Local conditions may be more or less severe than indicated by region classification A severe classification is where weather conditions result in signifi...

Page 27: ...liate thereof liable in any respect for any injury or damage to the building or structure in which the fireplace has been installed or to the persons or property therein arising out of the use misuse...

Reviews: