background image

19

When using approved factory built metal chimneys, you
must have at least 2" of clearance when going through
a wall or next to a wall. A typical factory chimney instal-
lation is shown on figure 9.

INSTALLING YOUR WOODCHUCK

Most of the Woodchuck furnace is factory assembled.
The factory assembly should be located as detailed in
the PLACEMENT AND MINIMUM CLEARANCES sec-
tion and on figure 7.

Remaining assembly will consist of mounting the con-
trols, draft and circulating blowers, filter box if used, and
electrical connection. These details will be provided af-
ter stove pipe and air duct installation.

STOVE PIPE INSTALLATION

Install your Wood/Coal unit as close to the chimney as
possible with a minimum of elbows. We recommend no
more than two elbows. The maximum horizontal run
should not exceed 6 feet with a 1/2" rise per foot. The
pipe should maintain a minimum of a 1/2" rise per foot
and NEVER be installed closer than 18" from combusti-
bles. Exceeding these recommendations normally rep-
resents creosote build-up, a smoking furnace, or one
with poor draft.

When connecting stove pipe, all joints should be se-
cured with at least three #10 sheet metal screws.

NOTE:

If it is absolutely necessary to make a run

greater than 6 feet (not recommended), use extra sup-
port brackets every 3 ft.

The connection to the wood furnace’s collar must also
be more than just a snug fit. Drill holes through the
Woodchuck’s collar and secure with sheet metal
screws. Mark each connection for cleaning. This will
prevent frustration when matching up your hole pattern
again.

DAMPERS IN STOVE PIPES

A manual damper may be installed at a safe convenient
place between the barometric damper and the chimney.
In the event of chimney fire, it can quickly be closed
reducing draft to the chimney. See figure 10.

INSTALLATION OF A BAROMETRIC

DRAFT

Some codes and NFPA require draft regulators in the
chimney connector of wood or coal furnaces and boil-
ers, and manufacturers recommend their use with some
stoves. There is some doubt among wood heat experts
as to whether use of barometric draft regulators is wise.

Draft regulators limit the draft-the suction pulling air into
the appliance. A pivoted, counter-balanced flap is
pulled open by the draft when the draft reaches a criti-
cal amount (figure 10). This permits air to enter the
chimney, thus preventing the draft in the appliance from
rising any higher.

Use of draft regulators with oil-fired equipment is com-
mon. One objective is to keep the oil flame from being
blown out by excessive draft. This is more an annoy-
ance than a safety problem since most oil burners have
primary safety controls which stop the fuel flow into the
burner whenever the flame goes out, and modern
flame-retention burner design makes draft regulation al-
most unnecessary for this objective.

A second objective is to limit the amount of air passing
through the system in order to maintain high heat trans-
fer efficiency. Another desirable consequence is a de-
crease in peak chimney temperatures due to the added
air entering through the regulator.

High draft does not blow out the flames but fans them in
wood and coal burning equipment. An especially hot
fire can result. Control of the fire may be difficult, partic-
ularly if the wood burner is not airtight. Energy efficien-
cies may be adversely affected, and chimney fires may
be ignited. A barometric draft regulator can alleviate
these problems by limiting the flow of combustion air
into the appliance and by adding cooling air to the hot
flue gases.

However the cooling air may result in more creosote
accumulation, and if a chimney fire does start, it will be
more intense because of the draft regulator. Large
flows of air into the regulator will fan the fire in the
chimney. Thus the net effect of barometric draft
regulators is unclear-they help in some aspects, and
hurt in others. Note, though, that if a chimney is clean
so that chimney fires are impossible, a draft regulator
does no harm, and does help limit the intensity of the
fire in the appliance, and it helps prevent the flue gases
in the chimney from getting too hot. Barometric draft
regulators are recommended by JFPA for hand fired
thermostatically controlled solid fuel furnaces.

SUGGESTED TYPE
DAMPER

AIR HOLES

Summary of Contents for WOODCHUCK 2900

Page 1: ...08 2012 Installation must be made in accordance with local and state codes which may differ from manual Save these instructions M a n u f a c t u r e d b y Meyer Mfg Corp Phone 715 654 5132 Fax 715 6...

Page 2: ...a Woodchuck Pride in craftsmanship and engi neering have made your Woodchuck the finest heating appliance available to day Solid fuels are abundant and inexpensive Wood is our only renewable source of...

Page 3: ...e 13 Trouble Shooting 14 General Requirements 16 Placement and Minimum Clearances 16 Installation 16 Chimney Installation 18 Installing Your Woodchuck 19 Stove Pipe Installation 19 Installation of a B...

Page 4: ...Door Rapidly Can Cause A Flame To Flash Out The Door Use Caution When Opening Loading Door Unsafe To Load Coal Above Top Of Brick Keep Ash Pan Out Of Unit During Operation Ash Pan Can Get Very Hot As...

Page 5: ...Secondary Heat Exchange YES Listings UL391 CSA B366 1 M ETLM Firebox Chamber 6 10 cu ft MODEL526 SPECIFICATIONS Height 48 5 Width 26 Depth 28 Blower 850 to 1850 CFM Max BTU Capacity 150 000 Log Size 2...

Page 6: ...on air must be warm when it enters the firebox to further pro mote complete combustion Your Woodchuck furnace provides all these features and more Here is how when combustion air enters a Woodchuck fu...

Page 7: ...ng for continuous air movement even during periods of low heat output this stratification is not allowed to take place You are more comfortable and lose less heat through your ceil ings as illustrated...

Page 8: ...WITHIN MARKED INSTALLATION CLEAR ANCES INSPECT AND CLEAN FLUES AND CHIMNEY REGU LARLY UNDER CERTAIN CONDITIONS OF USE CREO SOTE BUILDUP MAY OCCUR RAPIDLY WAIT 10 SEC ON FIRST LATCH BEFORE RE FUELING...

Page 9: ...pass switch is also a start up switch When the switch is in the OFF AUTO position the draft blower will run de pendent on the thermostat setting upstairs If fire has dropped to a temperature that is b...

Page 10: ...ostat up to activate auto draft and proceed as with manual draft Once the unit is warmed up you can turn the low limit by pass switch to OFF This will allow the auto draft to shut off if the unit runs...

Page 11: ...nds to give off large quantities of volatile gas This gas may accumulate and possibly ig nite causing a backpuff To reduce back puffing open the fire door to the first safety latch position for 15 20...

Page 12: ...pit will not allow the required air for combustion Keep ash pit clean ASH REMOVAL Ash should always be put into an air tight metal con tainer CAUTION KEEP ASH PAN OUT OF UNIT DURING OPERA TION ASH PA...

Page 13: ...onth to keep it tuned up and limber OPTIONAL CATALYTIC COMBUSTOR FOR MODELS 2900 4000 NOTE Optional catalyst not recommended for Model 2900 4000 with 6 flue adapter Smoke spillage may oc cur out of do...

Page 14: ...n Switch blower to the off position Bad wall Ther mostat check by turning it up to 80 and if the draft blower does not turn on replace thermo stat Lo limit bypass on off Replace thermostat When starti...

Page 15: ...r how good the conditions The use of wet frozen or unseasoned wood The use of soft wood particularly those of high resin content such as plywood or blandex with glue Poor natural draft or an obstructi...

Page 16: ...or oil fired fur nace or as a central furnace ELECTRICAL SUPPLY 115 volts 60HZ 1 Phase less than 12 amps Install system with 0 2 static pressure Flue setting 06 W C Max to 04 W C Min Wood or coal rela...

Page 17: ...FROOFWITHIN10 HORIZONTALLY ALSOSEEFIGURE9 ACHIMNEYWHICHRISESWITHINHOUSEISBETTER INSULATEDTHANACHIMNEYWHICHISLOCATEDOUTSIDE THEHOUSEANDISEXPOSEDTOWEATHER THECHIMNEYFLUEMUSTHAVEACROSSSECTIONALAREA ATLEA...

Page 18: ...y MAKE SURE YOUR WOODCHUCK IS IN STALLED INTO A PROPER CHIMNEY For maximum safety and efficiency never install the Woodchuck furnace into the same chimney serving an other appliance A typical chimney...

Page 19: ...t experts as to whether use of barometric draft regulators is wise Draft regulators limit the draft the suction pulling air into the appliance A pivoted counter balanced flap is pulled open by the dra...

Page 20: ...he plenum top may be dangerous so make sure clearances are maintained For the Model 4000 allow at least 4 from ceiling to plenum The ducts fittings grilles and registers should be sized so that the to...

Page 21: ...R GRATE INSTALLATION FOR MODEL 526 1 Remove standard grates from firebox Assemble com plete shaker grate kit outside of unit Figure 16 2 Assemble the left front bar different from right front bar has...

Page 22: ...bled grate on the loading door lower frame The grate should be the upside down position Slide the grate front end first into the firebox allowing the front end to lower into the hearth area Once the b...

Page 23: ...ks that will fit between the bevel cut bricks 4000 Models with have just two 2 thick bricks with bevel cuts that will fit to the outer walls of the firebox 3 Place rectangular brick along side walls o...

Page 24: ...to form a 90 angle This angle points toward the rear of the firebox FIGURE18 INSTALLOPTIONALCATALYTIC COMBUSTOR MODEL2900 4000 SLOTS IN EXHAUST PIPE CATALYTIC ELEMENT RODS ON RETAINER ASSEMBLE MANUAL...

Page 25: ...he rear of the fur nace Slide in from the top side figure 21 INSTALL FILTER BOX The filter box is standard on Model 526 Installation in structions are included with Model 526 filter box 1 The filter b...

Page 26: ...rt control These connections have been routed to a terminal strip on the outside of the comfort control box for convenient connection 4 The circulating blower limit control is factory wired to the com...

Page 27: ...SHOCK OR BURN DISCONNECT AND LOCKOUT POWER SOURCE BEFORE SERVICING OR INSTALLING ELECTRICAL COMPONENTS FAILURE TO HEED MAY RESULT IN SERIOUS PERSONAL INJURY OR DEATH CAUTION ALL WIRING MUST MEET LOCAL...

Page 28: ...r Pin 13 05 0004 Handle Access Cover 14 801 2520 1 5Z 1 4x1 1 2 Bolt KEY NO PART NO DESCRIPTION 15 06 0215 Spring 16 814 2520 Z 1 4 Lock Nut 17 05 0002 Small Grate 18 05 0001 Large Grate 19 07 5267 Fr...

Page 29: ...2902 Ash Door 12 06 1014 Handle Knob Large 13 02 2901 Fuel Door KEY NO PART NO DESCRIPTION 14 06 2902 Fuel Door Gasket 15 07 2901 Side Brick Kit 4 pc 16 07 2902 Rear Brick Kit 2 pc 17 07 2904 Front B...

Page 30: ...1014 Handle Knob Large 10 06 1013 80 20 Selector Knob 11 06 1001 Ash Pan 12 06 0200 Door Pin KEY NO PART NO DESCRIPTION 13 02 2901 Fuel Door 14 06 2902 Fuel Door Gasket 15 02 2902 Ash Door 16 06 2903...

Page 31: ...2903 End Rail W 10 3 05 2904 Shaker Bar CC 130 4 05 2905 Shaker Rail WC 2900 05 4001 Shaker Rail WC 4000 5 05 2906 Sleeve WC 2900 05 4003 Sleeve WC 4000 6 05 2908 Handle WC 2900 E423 05 2907 Handle W...

Page 32: ...Bracket 9 08 0112 Kit Motor Clamp 2 COVER not shown 08 0100 COMFORT CONTROL Item 8 10 11 12 Not Included Order Separately DRAFT Wiring Decal See Next Page 9 KEY NO PART NO DESCRIPTION 1 08 0100 2 Box...

Page 33: ...33 46 2900 8 Forced Draft Wiring Diagram...

Page 34: ...Purchase Date Of Installation Name Of Installer Address Phone HOW TO READ YOUR SERIAL NUMBER Your serial number is located on your Certification Panel Example 0085 3582 Model Code Sequence of Build 0...

Page 35: ...g or negligence or from an attempt to repair the unit by any person not expressly authorized by Meyer Manufacturing Corporation to do the repair Limit of Obligation No one is authorized to make any ot...

Page 36: ...Box 405 Dorchester Wisconsin 54425 ManufacturedBy MEYERMANUFACTURINGCORPORATION CountyHwy A West P O Box 405 Dorchester Wisconsin54425 0405 Phone 715 654 5132 FAX 715 654 5513 1 800 325 9103 www meye...

Reviews: