3 Installation
page
15
ELC N6_N10-V3.1-09/11-GB subject to technical alterations
Digital: MIN und MAX
For certain operation modes the lamp power can be set to Maximum or Minimum
independent of the control voltage at SET VALUE. E.g.:
•
Lamp warm-up: maximum power or
•
Standby operation: minimum power
To this purpose the control inputs MAX and MIN respectively are set to High, whereby the
function MAX has the higher priority.
3.4.4 Table: lamp power
SET VALUE
MIN
MAX
Lamp power
0 – 10 V
LOW
LOW
stepless
Minimum – Maximum
0 – 10 V
HIGH
LOW
Minimum
0 – 10 V
LOW
HIGH
Maximum
0 – 10 V
HIGH
HIGH
Maximum