7 ND90 71 en
67
Device Information:
1 Device Information
1 Operation Unit
1 Tag
ND9000
2 Confguration
2 Positioner
2 Description
ND9000
3 Calibration
3 Date
27.8.2001
4 Manually Stroke Valve
4 Message
ND9000
5 Monitoring
5 Long tag
ND9000
6 Lifecycle Diagnostic
7 Counter Diagnostics
8 Online Diagnostics
1 Device Type
ND9100H
9 Valve Offline Tests
2 VC PCB Serial Number
1650518510
Advanced Configuration
3 HART PCB Serial Number
1647317020
4 Device Serial Number
PH17100205
5 HART Board HW revision
H033592-1.20
6 Software rev
193
7 HART Board Dac SW revision
UNKNOWN
Configuration
Position Control
1 Position Control
Performance Level
Aggressive (A);Fast (b);
Optimum (C);
Stable (d); Maximum Stability (E); Capacity Booster, Aggressive (A1); Capacity Booster, Fast
(b1); Capacity Booster, Optimum (C1);Capacity Booster, Stable (d1)
2 Assembly Related
3 Signal Modification
Assemby Related
1 Actuator Type
Double Acting,
Single Acting
2 Valve Acting Type
Rotary,
Linear with Compensation, nelesCV Globe, Linear without Compensation
MENU
3 Valve Rotation Direction
Clockwise to Close,
Counterclockwise to Close
4 Dead Angle (a0)
0,00 %
METHOD
5 Positioner Fail Action
Close,
Open
6 Positoner Transmitter Directions
Normal Direction, Reverse Direction,
Not Installed
Editable variable
Signal Modification
Read-only variable
1 Direction
Rising Setpoint to Open,
Rising Serpoint to Close
2 Valve Position Limit LOW
0,00 %
3 Valve Position Limit High
100,00 %
4 Travel Rate Open
0,00 %
5 Travel Rate Close
0,00 %
6 Low Cut-Off
2,00 %
7 High Cut-Off
100,00 %
8 Split Range LOW
0,00 %
9 Split Range HIGH
100,00 %
Bypass signal modification
No
; Yes
Calibration
Automatic Calibration
1 Automatic Calibration
1 Start Automatic Calibration
2 One Point Calibration
One Point Calibration
1 Start One Point Calibration
Manually Stroke Valve
Manual mA Setpoint
Manual percent Setpoint
Monitoring
1 Loop Current
2 Setpoint
3 Target Position
4 Valve Position
5 Device Temperature
6 Supply Pressure
7 Actuator Pressure Difference
Lifecycle Diagnostic
Warning Limits for Trends
1 Warning Limits for Trends
1 Steady State Deviation
3,00 %
2 Dynamic State Deviation
20,00 %
3 Stiction Low
0.0 bar
4 Stiction High
4.0 bar
5 Load for Open Low
0.0 bar
6 Load for Open High
0.0 bar
Counter Diagnostics
Counters
1 Counters
1 Total Operation Time
1.10 h
2 Warning Limits for Counters
2 Total Valve Travel
0,04
3 Total Valve Reversals
0
4 Total Actuator Travel
0,04
5 Total Actuator Reversals
0
6 Total Spool Valve Travel
0,02
7 Total Spool Valve Reversals
0
8 Total Setpoint Travel
0,18
9 Total Setpoint Reversals
0
Warning Limits for Counters
1 Total Operation Time
216000.0h
2 Total Valve Travel
250000
3 Total Valve Reversals
1000000
4 Valve Reversals Trend
10000
5 Daily Valve Reversals while Stable Setpoint
5000
6 Total Actuator Travel
250000
7 Total Actuator Reversals
1000000
8 Total Spool Valve Travel
10000000
9 Total Spool Valve Reversals
10000000
Setpoints Reversals Trend
10000
Online Diagnostics
1 Device Status
Device Status
List active alerts
2 Alarm Limits
3 Events
Alarm Limits
Steady State Deviation
1 Steady State Deviation
1 Steady State Deviation High Limit
5 %
2 Supply Pressure
2 Steady State Deviation Latch Time
30sec
3 Temperature
4 Stiction
Supply Pressure
5 Load for Opening
1 Supply Pressure Low Limit
1.4 bar
6 Valve Position
2 Supply Pressure High Limit
8.0 bar
3 Supply Pressure Latch Time
30 sec
Events
1 All Events
Temperature
2 Notify Events
1 Temperature Low Limit
-40.0 deg C
3 Warning Events
2 Temperature High Limit
85.0 deg C
4 Error Events
3 Temperature Latch Time
120.0 sec
5 Alarm Events
6 Failsafe events
Stiction
1 Stiction Low Limit
0.0 bar
2 Stiction High Limit
10.0 bar
3 Stiction Latch Number
10
Load for Opening
Valve Offline Tests:
Select which Offline Test to start:
1 Load for Opening Low Limit
0.0 bar
1 Start Offline Tests
1 Multipoint Step Test
2 Load for Opening High Limit
0.0 bar
2 Test Key Figures
2 Dynamic Loop Test
3 Load for Opening Latch Number
10
3 Valve Analysis Test
4 Valve Deadband Test
Valve Position
1 Valve Position Low Limit
-20.0%
2 Valve Position High Limit
120.0%
3 Valve Position Latch Time
30.0 sec
Test Key Figures:
Multipoint Step Test Key Figures:
1 Multipoint Step Test Key Figures
1 Start Position
50.00
2 Dynamic Loop Test Key Figures
2 End Position
55.00
3 Valve Analysis Test Key Figures
3 Testing Time
5.00
4 Valve Deadband Test Key Figures
4 Dead Time Td
0.08
5 Step Response Time T86
0.62
6 Overshoot
1.17
7 Travel Gain
1.00
Dynamic Loop Test Key Figures:
1 Start Position
0.00 %
2 End Position
100.00 %
3 Total Testing Time
30.00 sec
4 Max. Dyn. Error
3.67 %
5 Setpoint at Error
87.07 %
Valve Analysis Test Key Figures:
1 Target Position
50.0 %
2 Steady Time
12.0 sec.
3 Ramp Time
30.0 sec.
4 Static Hysteresis
1.2 %
5 Sensitivity
5.2 %
6 Load for Opening
0.6 bar
7 Seat Load
4.8 bar
8 SR O2C Close
0.0 bar
9 SR O2C Open
0.0 bar
SR C2O Close
0.0 bar
SR C2O Open
0.0 bar
Valve Deadband Test Key Figures:
1 Start Position
50,00 %
2 Testing Time
10
3 Deadband
0.1
ND9100H - Dev v4, DD v2:
Operation Unit
Positioner