7 ND90 71 en
63
7.
OPTIONS OF VALVE CONTROLLER
T
Internal 2-wire (passive) position transmitter. Analog position
feedback signal, output 4–20 mA, supply voltage 12–30 V DC,
external load resistance 0–780 Ω.
ND91_HXT, ND91_HZT, ND92_HXT, ND93_HXT, , ND93_HZT,
ND94_HXT:
II 1 G Ex ia IIC T6...T4 Ga
II 1 D Ex ta IIIC T90 °C Da
II 2 G Ex ib IIC T6...T4 Gb
II 2 D Ex tb IIIC T90 °C Db
Ui ≤ 28 V, Ii ≤ 120 mA, Pi ≤ 1 W, Ci ≤ 22 nF, Li ≤ 53 μH,
external load resistance 0–690 Ω.
ND91_HXT, ND91_HZT, ND92_HXT, ND93_HXT, ND93_HZ, T,
ND94_HXT:
II 3 G Ex nA IIC T6...T4 Gc
II 3 D Ex tc IIIC T90 °C Dc
Ui ≤ 30 V, Ii ≤ 152 mA
II 3 G Ex ic IIC T6...T4 Gc
II 3 D Ex tc IIIC T90 °C Dc
Ui ≤ 30 V, Ii ≤ 152 mA, Pmax = device limits itself, Ci ≤ 22 nF,
Li ≤ 53 μH, external load resistance 0–780 Ω.
ND91_HUT, ND92_HUT, ND94_HUT and ND93_HU1T:
Class I, Division 1, Groups A, B, C, and D; T4/T5/T6
Ex ia IIC T4/T5/T6 Ga
Class I, Zone 0 AEx ia IIC T4/T5/T6 Ga
Ui ≤ 28 V, Ii ≤ 120 mA, Pi ≤ 1 W, Ci ≤ 22 nF, Li ≤ 53 μH,
external load resistance 0–690 Ω.
Class I, Division 2, Groups A, B, C, and D; T4/T5/T6
Ex nA IIC T4/T5/T6 Gc or Ex nA ia IIC T4/T5/T6 Gc Ga
Class I, Zone 2 AEx nA IIC T4/T5/T6 Gc or Ex nA ia IIC T4/T5/T6 Gc Ga
Ui ≤ 30 V, Pmax = device limits itself, Ci ≤ 22 nF, Li ≤ 53 μH, external
load resistance 0–780 Ω
ND92_HE1T, ND92_HE2T, ND92_HE4T, ND92_HE5T,
ND92_HE7T, ND93_HE1T, ND93_HE5T, ND93_HE7T:
Ui ≤ 30 V, Pmax = device limits itself,
external load resistance 0–780 Ω.
Applicable to 5. sign "H".
R
Remote mounting
Applicable only to 3. sign "1"
Requires always external position measurement. For rotary
actuator see accessories type code.
Output values for:
HART
Uo(Voc) = 3.53V, Io(Isc) = 12.6mA, Po = 11.1 mW, Co(Ca) = 10nF,
Lo(La) = 10μH.
F
OUNDATION
fieldbus and Profibus
Uo(Voc) = 5.0V, Io(Isc) = 17.8mA, Po = 22.2mW, Co(Ca) = 10nF,
Lo(La) = 10μH.
G
Exhaust adapter. ND9100: 1x 1/2 NPT thread, ND9200 and
ND9300: 2 x 1/2 NPT thread.
C
Arctic temperature option.
Temperature range -53 – +85 °C / -64 – +185 °F
Applicable to 3. sign "2 and 3"
Applicable to 6. sign "X", "X7", "E1, "E2", "E7" and "U"
Not applicable to 7. sign J (External junction box)
Note, Limit switch may limit the temperature range
J
ND91_H, ND94_H, ND92_H and ND93_H:
External junction box for all 4–20 mA wirings, including position
transmitter, if applicable. Junction box is connected to the
enclosure, 2 pcs. M20 x 1.5 conduit entry.
ND91_F, ND92_ F, ND94_F, ND93_F, ND91_P, ND92_P, ND94_P
and ND93_P:
External junction box for wirings, including option for parallel
connection of external surge protector.
Junction box is connected to the enclosure,
2 pcs. M20 x 1.5 conduit entry.
Applicable to 6. sign "N", "N7", "X", "X7", "Z", "E1" ,"E2" or "E7".
Y
Special construction.
8.
LIMIT SWITCH TYPE
Inductive proximity switches
, 2 pcs.
IP66 / NEMA 4X enclosure. M20 x 1.5 conduit entry (2 pcs.).
Option E2: 1/2 NPT conduit entry (2 pcs.).
Limit switches applicable only with ND9100, ND9200 and
ND9300
D33
Metso; SST Sensor Dual Module, NO, 8–125 V DC / 24–125 V AC
Temperature range -40° to +82 °C / -40° to +179 °F.
Applicable to 6. sign "N", "N7", "E1", "E2", "E5" and "E7".
Usable up to SIL3 acc. to IEC61508.
D44
Metso; Namur Sensor Dual Module, 6–29 V DC, > 3 mA; < 1 mA.
Temperature range -40° to +82 °C / -40° to +179 °F.
Applicable to 6. sign "N", "N7", "U", "E1", "E2", "E5" and "E7".
Usable up to SIL3 acc. to IEC61508.
I02
P+F; NJ2-12GK-SN, 2-wire type, DC; > 3 mA; < 1 mA, NAMUR NC.
Temperature range: -40° to +85 °C / -40° to +185 °F.
Not applicable to 6. sign "E4".
Usable up to SIL3 acc. to to IEC61508
NOTE:
In safety-related applications the sensor must be operated
with a qualified fail safe interface, such as P+F KFD2-SH-EX1.
I09
P+F; NCB2-12GM35-N0, 2-wire type, DC; > 3 mA; < 1 mA,
NAMUR NC
Temperature range: -25° to +85 °C / -13° to +185 °F.
Not applicable to 6. sign "E4"
Usable up to SIL2 acc. to IEC61508.
I32
Omron E2E-X2Y1, 2-wire type; AC; <100 mA; 24–240 V AC.
Temperature range: -40° to +85 °C / -40° to +185 °F.
Applicable to 6. sign "N", "N7", "E1", "E2", "E5" and "E7".
I41
P+F, NJ4-12GK-SN, 2-wire, DC; > 3 mA; < 1 mA, NAMUR NC
Temperature range -50 ... +85 °C /-58 ... 185 °F)
Applicable to 6. sign "N", "N7", "X", "X7", "U", "E1", "E2" or "E7".
Note that device may limit temperature range.
I45
P+F; NJ3-18GK-S1N, 2-wire type, DC; > 3 mA; < 1 mA, NAMUR NO.
Temperature range: -25° to +85 °C / -13° to +185 °F.
Not applicable to 6. sign "E4".
Usable up to SIL3 acc. to IEC61508.
I56
ifm; IFC2002-ARKG/UP, 2-wire type, DC; 150 mA, 10–36 V DC,
leakage current < 0.6 mA.
Temperature range: -20° to +85 °C / -4° to +185 °F.
Not applicable to 6. sign "X", "X7", "Z", "U" and "E4".
Mechanical micro switches,
2 pcs.
IP66 / NEMA 4X enclosure.
M20 x 1.5 conduit entry (2 pcs.).
Option E2: 1/2 NPT conduit entry (2 pcs.).
Limit switches applicable only with ND9100, ND9200 and
ND9300
K05
Omron D2VW-5, 3 A - 250 V AC, 0.4 A - 125 V DC, 5 A - 30 V DC.
Temperature range: -40° to +85 °C / -40° to +185 °F.
Not applicable to 6. sign "X", "X7", "Z", "U" and "E4".
K06
Omron D2VW-01, gold plated contacts, 100 mA - 30 V DC /
125 V AC.
Temperature range: -40° to +85 °C / -40° to +185 °F.
Not applicable to 6. sign "X", "X7", "Z", "U" and "E4".
Bus powered mechanical micro switches,
2 pcs.
Applicable to ND9000F and ND9000P only.
IP66 / NEMA 4X enclosure. M20 x 1.5 conduit entry (2 pcs.). Option
E2: 1/2 NPT conduit entry (2 pcs.).
B06
Omron D2VW-01, gold plated contacts; Bus Powered,
no external power needed.
Temperature range: -40° to +85 °C / -40° to +185 °F.
Not applicable to 5. sign "H”.
Not applicable to 6. sign "E4".
9.
OPTIONS OF LIMIT SWITCH
Y
Special construction.