background image

14

TYPE CODE

PNEUMATIC POSITIONER NP 700

1.

2.

3.

4.

5.

6.

NP

7

2

4

S

/

S1

K

1. sign

PRODUCT GROUP

NP

Pneumatic positioner

2. sign

SERIES CODE

3. sign

INPUT SIGNAL RANGE

0

4-20 mA,  only with options B and B1 (6th sign).

2

20-100 kPa (0,2-1,0 bar/3-15 psig)

4. sign

PILOT VALVE
SIZE

CONNECTIONS
S, C1, C2

3

Ø4 mm LC

1/4 NPT

4

Ø4 mm

1/4 NPT

6

Ø6 mm

1/4 NPT

7

Ø6 mm HC

3/8 NPT

9

Ø4 mm LC
3-way pilot valve,  single
action, applicable only
with B1J 8, QP 1, QP 2
and DA/RA. 5th sign
always S or A.

1/4 NPT

5. sign

ACTION

Double action,  without sign.

S

Single action,  specified in the option sticker.

A

Single action, linear motion
applicable only to Metso Automation D/R series
diaphragm actuator, max. stroke 57 mm (2 1/4 in).

6. sign

OPTIONS

Standard (IP 54 enclosure).
6th sign S1 or S2 always to be defiened.
Temperature range -40 ˚C - +90 ˚C/ -40 ˚F - +194 ˚F.

B

Flameproof enclosure I/P converter (IP65),
BVS-approval, EEx d IIC T6. Input signal range 4-20 mA.
M20x1.5 conduit entry.  3rd sign always 0.
Temperature range -40 ˚C - +55 ˚C/ -40 ˚F - +131 ˚F.

B1

Flameproof enclosure I/P converter (IP65),
FM/CSA-approval, Class 1, Div. 1, Groups B, C, D.
Input signal range 4-20 mA. 1/2 NPT conduit entry.
3rd sign always 0.
Temperature range -40 ˚C - +55 ˚C/ -40 ˚F - +131 ˚F.

GN

For natural gas.  Exhaust adapter,  3/4 NPT thread.
Not usable inside with options B and B1.

R

Water and dustproof enclosure IP65/NEMA 4 and 4X.
 Not available with option GN.

H

High temperature construction. Viton diaphragm and
seals. Not available with options B, B1, A, A1 and K.
Temperature range -10 ˚C - +120 ˚C/ +14 ˚F - +248 ˚F.

S1

Positioner with attachment face acc.  to standard
VDI/VDE 3845,  equipped with H-clip.  When
positioners are separate deliveries, VDI/VDE ear is
supplied.
Not applicable to globe valve actuators (5th sign A).

S2

Positioner with attachment face acc. to Metso
Automation, equipped with C-clip.
Not applicable to globe valve actuators (5th sign A).
Used only with non-MA limit switches,  etc..

J7

Octagonal shaft and special mounting kit.

J30

Square shaft and special mounting kit

A

Pressure gauges,  scale bar/psi/kPa,  basic material
brass, nickel plated, housing stainless steel, glycerine
filled.  5th sign always to be defined. 
Temperature range -40 ˚C - +70 ˚C/ -40 ˚F - +158 ˚F.

A1

By-pass, 20-100 kPa/0.2-1.0 bar/3-15 psig. Only for
single action diaphragm actuator. Pressure gauges,
scale bar/psi/kPa, basic material brass, nickel plated,
crust stainless steel, glycerine filled.  5th sign always A. 
Temperature range -40 ˚C - +70 ˚C/ -40 ˚F - +158 ˚F

Q

Aluminium cover,  rised position pointer

Y

Special construction.

C

Special cam.

EXTERNAL CONNECTION
PARTS

K

Filter regulator for supply air type BELLOFRAM 51FR.
Pressure gauge, scale bar/psi/kPa, basic material brass,
nickel plated, housing stainless steel, glycerine filled.
Temperature range -18 ˚C - +52 ˚C / -10 ˚F - +125 ˚F.
Filter size 5 

µ

m. Not available with HC-pilot (4th sign 7)

Specified in the option sticker.

In connection with the Ø6 HC-pilot valve (4th sign 7)
must be used large capacity filter regulator (not K)
for actuator bigger than B1C 40 and B1J 32.
Installation with mounting bracket.

L

M20x1.5 / 1/2 NPT conduit entry nipple.
EEx d IIC-approval.  Available only with option B.
Specified in the option sticker

18

Summary of Contents for NE700/S1

Page 1: ...POSITIONERS Series NP Installation Maintenance and Operating Instructions 7 NP 72 en Issue 5 02 ...

Page 2: ...TENANCE 10 8 1 Supply air filter 10 8 2 Pilot valve 10 8 3 Replacement of the diaphragm 11 9 TROUBLE SHOOTING 11 10 OPTIONS 11 10 1 NP700 GF and NP700GN natural gas construction 11 10 2 NP700 R dust proof construction IP 65 11 10 3 NP700 A with pressure gauges 11 11 TOOLS 11 12 ORDERING SPARE PARTS 11 13 DRAWINGS AND PARTS LISTS 12 13 1 Exploded view and parts list 12 13 2 Mounting parts for B1C6 ...

Page 3: ... difference pressure until the compression force of the feedback spring generated by the change in position is in equilibrium with the force generated by the signal pressure Thus each signal pressure value corresponds to a single actuator position If an external force acts on the actuator shaft the shaft tends to move in the direction of the torque This alters the position of the spool via the fee...

Page 4: ...TION Do not dismantle a pressurized positioner Dismantling a pressurized positioner will result in uncontrolled pressure release Always isolate the relevant part of the pipeline release the pressure from the positioner and the piping Failure to do this may result in damage or personal injury CAUTION Beware of the moving parts when positioner is operated 2 M O U N T I N G O N T H E METSO AUTOMATION...

Page 5: ...emove the limit switch before the adjustment of the positioner 1 Loosen the cover screws Note the position of the shaft relative to the positioner when removing the limit switch 2 When the adjustment of the positioner is done operate the actuator until the valve is in the closed or open position 3 Note the position of the actuator and valve when mounting the limit switch on the actuator Make sure ...

Page 6: ...2 16 3 6 220 6 7 409 1 2 x x x x 4 5 11 8 18 3 5 6 4 5 11 20 25 13 793 27 1648 3 4 x x x x x x x x 8 5 21 17 38 7 5 19 15 33 32 322 53 3234 106 6468 1 x x x x x 33 74 30 64 60 130 QP Stroke vol dm3 in3 NPT 1 4 3 8 1 2 6 4 10 8 12 10 1 C 0 62 37 3 8 x x 1 5 2 1 5 2 2 C 1 08 66 3 8 x x 2 3 5 2 3 5 3 C 2 18 133 3 8 x x 3 5 2 3 4 C 4 34 265 3 8 x x 6 10 4 6 5 C 8 7 531 3 8 x x 7 10 6 C 17 5 1068 3 4 x...

Page 7: ...ose valve Cam segments B 0 100 A 0 50 A 50 100 4 Increasing input signal to close valve Spring to open valve Cam segments B 0 100 A 0 50 A 50 100 WARNING Valve closes exceptionally counterclockwise Unsuitable for Q R T5 F and L series valve NOTE Reverse piping for ST actuators Spring and piston in the opposite position from shown SINGLE ACTING SPRING TO OPEN 5 Increasing input signal to close valv...

Page 8: ...ng segments are roughly 15 20º 4 PRELIMINARY ACTIONS FOR THE ADJUSTMENT Setthevalve sopenandclosedlimitswiththeactuatorlimiterscrews see thevalveinstructionmanual Thechangeoverpiece 46 andthecam 29 must be in correct positions Check the pilot valve size from Table 2 The adjustment must always be carried out when the supply pressure has been changed Please note that operating of the valve is requir...

Page 9: ...lue The valve should be entirely open at 100 i e 1 0 bar 15 psig or 0 2 bar 3 psig The valve should start to operate to closed direction at 98 i e 0 98 bar 14 0 psig or 0 22 bar 3 2 psig The range i e turning angle changes when the effective lenght of the spring 60 is increased or decreased by turning the range adjustment nut 60 3 See Fig 11 4 The zero and range adjustments affect each other so st...

Page 10: ...ntenance is not necessary The need for maintenance depends on the quality of the instrument air see Section 2 5 If there is need for servicing proceed according to the following sections 8 1 Supply air filter The supply air filter 50 is located in the supply air connection S the filter can be removed and cleaned with e g compressed air segment C segment D segment E shift Roller contact point when ...

Page 11: ... actuator changeover piece or cam position wrong see Fig 4 actuator or valve jammed 2 The actuator reaches final position with a small signal pressure change the tube installation between positioner and actuator the changeover piece or the cam position wrong 3 Inaccurate positioning pilot valve dirty beam 5 pushes pilot valve spool sideways diaphragm damaged actuator torque too low supply pressure...

Page 12: ...13 DRAWINGS AND PARTS LISTS 13 1 Exploded view and parts list 12 ...

Page 13: ...over pice 47 2 O ring X 48 1 Protective plate 49 2 Hexagon nut 50 1 Filter 51 2 Bearing Item Qty Description Recommended spare part 52 1 Coupling 55 1 Gasket X 56 1 Screw 57 1 Grub screw 58 1 Support plate 59 2 Barrel nut 60 1 Spring 62 1 Hexagon plug 64 1 Body 65 1 Lock ring 67 1 Zero screw 68 2 Spring 69 2 Guide 70 1 Pressure gauge block 71 3 O ring X 72 3 Screw 73 1 Pressure gauge 74 2 1 Pressu...

Page 14: ...13 2 Mounting parts for B1C6 502 and B1J8 322 actuators S1 Item Qty Description 1 1 Mounting bracket 2 1 Draught piece 3 4 Washer 4 4 Screw 28 1 Screw 29 2 Screw 36 1 Coupling jacket 14 ...

Page 15: ...on 1 1 Mounting bracket 2 2 Coupling half 3 1 Adapter 4 4 Screw 5 4 Hex nut 6 1 Screw 7 4 Screw 8 4 Washer 9 4 Screw 10 4 Washer Drive female spline Item Qty Description 1 1 Mounting bracket 2 1 Ear 4 4 Screw 28 4 Screw 29 1 Screw 30 4 Screw 35 1 Coupling 36 1 Coupling jacket 15 ...

Page 16: ...rs S2 Item Qty Description 1 1 Mounting bracket 2 1 Draught piece 3 2 Washer 4 2 Screw 5 1 Bracket 6 1 Washer 7 1 Screw 8 2 Washer 10 1 Rod 11 2 Bushing 12 2 Screw 13 2 Stud B1C6 only 14 2 Hexagon nut B1C6 only 26 2 Locking nut 27 2 Washer 28 2 Screw 16 ...

Page 17: ...for B1C25 502 and B1J25 322 actuators S2 Item Qty Description 1 1 Mounting bracket 2 1 Draught piece 3 2 4 Washer 4 2 4 Screw 8 2 Washer 9 2 Screw 10 1 Rod 11 2 Bushing 12 2 Screw 26 2 Locking nut 27 2 Washer 28 2 Screw 17 ...

Page 18: ...1 and K Temperature range 10 C 120 C 14 F 248 F S1 Positioner with attachment face acc to standard VDI VDE 3845 equipped with H clip When positioners are separate deliveries VDI VDE ear is supplied Not applicable to globe valve actuators 5th sign A S2 Positioner with attachment face acc to Metso Automation equipped with C clip Not applicable to globe valve actuators 5th sign A Used only with non M...

Page 19: ......

Page 20: ...x 1 508 852 8172 Latin America Av Independéncia 2500 Iporanga 18087 101 Sorocaba São Paulo Brazil Tel 55 15 3235 9700 Fax 55 15 3235 9748 49 Asia Pacific 501 Orchard Road 05 09 Wheelock Place 238880 Singapore Tel 65 673 552 00 Fax 65 673 545 66 Middle East Roundabout 8 Unit AB 07 P O Box 17175 Jebel Ali Freezone Dubai United Arab Emirates Tel 971 4 883 6974 Fax 971 4 883 6836 www metsoautomation c...

Reviews:

Related manuals for NE700/S1