[3]: The failure from the source channel
may be retransmitted as the constant “special”
value on the output. If
Disabled
mode is selected, the value is set to 0, except for to
mode 4-20mA when it is set to 3.6 mA.
12.3 Communication settings
The window is divided into two sub-windows: for Ethernet and for RS485
communication settings. Confirm
and cancel
buttons are common for both
sub-windows, clicking on these buttons results in toggles to the Main Menu.
Fig. 12.3 An example
view of the ‘Communication’ settings window – ‘Ethernet’ tab.
12.3.1 Ethernet port
To ensure proper communication between the device and the master system, all
communication parameters need to be configured.
Main Menu
Communication
Ethernet
IP address:
192.168.0.10
[1]
ModbusTCP port:
502
[2]
Mask:
255.255.255.0
[1]
Gate:
192.168.0.1
[1]
[1]: These parameters should correspond to the network where the recorder is intended
to operate.
[2]: It is recommended to use the 502 port dedicated to Modbus TCP, port 80 is not
allowed (reserved for websites).
12.3.2 RS-485 port
Recorder RS-485 port settings must correspond to the master device settings.
Main Menu
Communication
RS485 COM
Baud Rate
115200
(1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200)
[1]
Parity
EVEN
(NONE, EVEN, ODD)
[2]
ModbusRTU Address: 1
(1, 2, .., 247)
[3]
[1]: Baud Rate should be set to the highest possible value. For high distances or high
interference level, data transmission speed may need to be decreased. Low
transmission speed extends the reading time.