![metrofires Ambie One Installation & Owner'S Operation Manual Download Page 4](http://html1.mh-extra.com/html/metrofires/ambie-one/ambie-one_installation-and-owners-operation-manual_1779484004.webp)
4
Measurements listed below are the minimum required, stated
in millimetres. Measurements are taken from the following
reference points as illustrated:
- From the nearest combustible wall or surface
(A, B, D, E, G, H)
- From the Metro’s flue centre (A, B, C, D)
- From the outermost point of the Metro’s cabinet
construction (E, F, G, H)
- To the edge of the ash floor protectors non-combustible
surface (C, F, I, J, K, L, M)
Specifications were correct at the time of printing, but may
alter and those detailed within should be used only as a
guide. If in doubt, please consult your Metro retailer.
Note: Both wetback
connections are 140mm
left of the flue centre,
facing the Metro/wall.
Clearance chart
Metro clearances and specifications
(Minimum clearances shown are in mm, with a Pioneer double flue shield fitted)
Minimum installation clearances with a Pioneer double flueshield fitted (mm)
Wetback
Dimensions
Clean Air Models
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
Width
Depth Height
Ambie One
250
538
589
391
100
275
250
100
839
825
1142
960
427
350
540
577
464
717
Ambie Plus
267
685
658
462
125
275
350
100
925
905
1317
1110
506
360
550
671
550
761
150mm (One)
167mm (Plus)
Pioneer manufacture an extensive range of what Pioneer
term “Ash Floor Protectors” which comply with the minimum
floor protector requirement of AS/NZS2918:2001, and can be
installed with any freestanding Metro wood fire.
Metro freestanding wood fires do not require an insulated floor
protector as they comply with the minimum floor protector
requirements of AS/NZS2918:2001. These minimum floor
protector requirements are;
• They must be of adequate size to give appropriate wall,
rear and front clearances/projections as detailed in the
clearance chart illustrated below. Note;
- The floor protector must extend 100mm horizontally to
the rear and 200mm horizontally to each side directly
below the door opening, and 300mm forward of the door
opening.
- The upper surface of the floor protector must be made of
non combustible material.
• A suitable floor protector for a Metro freestanding wood
fire is therefore any non-combustible material which could
include;
- Ceramic tiles with grouted joints fixed directly to timber
flooring.
- A sheet of toughened glass, panel steel etc. laid directly
onto a wooden or other combustible floor.
Note: If being installed onto a concrete or non-combustible floor a floor
protector is not required.
Floor protector size, construction and fitting