Metrix ST5484E Manual Download Page 6

 

 

Document 9162 

Manual - ST5484E 2-Wire Seismic Vibration Transmitter 

Page 6 of 7 

Rev. T (Oct 2013)

 

 

 

Figure 5 – Top view showing optional dynamic output 
connections on transmitters with terminal blocks 

When attaching conduit to the transmitter, observe the following: 
 

 

Because the transmitter is sensitive to vibration, avoid unsupported lengths of conduit and excessive mass (such as 
large hubs or junctions) hanging directly off the end of the transmitter.  These can introduce unwanted vibrations 
that do not reflect actual machinery vibration.  These can also introduce mechanical stresses that cause the 
transducer to fail prematurely.  
 

 

A “Y” type conduit elbow such as the Metrix 8200 is preferred because it prevents the conduit from extending too 
far away from the transmitter, thus limiting the likelihood of breakage by personnel working on or near the machine.  
It also precludes long unsupported lengths of conduit directly aligned with the transmitter’s bore (longitudinal axis) 
as noted in the bullet above. 
 

 

Avoid attachment of rigid conduit directly to the transmitter; instead, use a small length of flexible conduit to 
mechanically isolate the transmitter from vibration that might occur in rigid conduit. 
 

 

If a 1-inch to 3/4-inch reducer is used at the elbow, a smaller diameter flexible conduit can be used.     

 

7.  Calibration 

The ST5484E transmitter has been factory calibrated for the full scale 
vibration level marked on the label.  If the calibration is in doubt the 
unit can be verified in the field by following the procedures outlined 
below.  Note that there are no Zero and Span adjustments on the 
transmitter. Also note that the transmitter uses a true RMS amplitude 
detection circuit; units supplied with a full scale range in peak units 
scale the underlying RMS measurement by a factor of 1.414 to provide 
a “derived peak” rather than true peak measurement.  

 

7.1  Zero Verification

    In the absence of vibration the output 

current should be 4 mA ±0.1 mA.  If the ambient vibration is more 
than 2% of full scale, the transmitter should be removed from the 
machine and placed on a vibration free surface for this 
measurement.   Often a piece of foam can be used to isolate the 
transmitter from external motion. 
 

7.2  Span Verification

   Subject the transmitter to a known 

vibration within the full scale range marked on the label.  If using a 
portable vibration shaker where it can be tested at full scale, the 
output should be 20 mA ±0.5 mA.   

   

8.  Optional Dynamic Output 

The transmitter can be ordered with an optional dynamic output.  
Transmitters supplied with this option can be identified by the 
presence of 4 flying leads instead of 2 (Figure 4), or 4 terminal connections instead of 2 (Figure 5).   

Figure 4 – Top view showing optional dynamic output 
connections on transmitters with flying leads 

Summary of Contents for ST5484E

Page 1: ...nter bore surfacing tool This tool can be used with a portable drill equipped with a magnetic base but care must be taken so that the tapped and threaded hole is perpendicular to the machined surface...

Page 2: ...n This is the minimum voltage required at the transmitter not the power supply after all other voltage drops across field wiring and receiver input impedance have been accounted for with the maximum 2...

Page 3: ...ltage 105 1V 50 ohms 19 1 V 21 2 VDC 3 3 Explosion Proof Installation In Hazardous Locations CSA ST5484E transmitters are CSA certified explosion proof Class I B C D Class II E F G Connect the field w...

Page 4: ...wer supply must be provided Connect the transmitter field wiring using standard instrumentation practices Scaling of the display is on the basis of the range of the transmitter The measurement paramet...

Page 5: ...housings as depicted in Figures 2 The horizontal direction usually incurs more vibration because most machines are more compliant in the horizontal axis than the vertical axis i e the machine s found...

Page 6: ...onduit can be used 7 Calibration The ST5484E transmitter has been factory calibrated for the full scale vibration level marked on the label If the calibration is in doubt the unit can be verified in t...

Page 7: ...nput impedance and they will load this signal resulting in attenuation of as much as 20 to 30 Refer to Table 1 at right showing the nominal attenuation expected for a given input impedance In all case...

Reviews: