Metrix ST5484E Manual Download Page 2

 

 

Document 9162 

Manual - ST5484E 2-Wire Seismic Vibration Transmitter 

Page 2 of 7 

Rev. T (Oct 2013)

 

 

 

3. Wiring   

The ST5484E is connected like any other loop powered transmitter.  The following is a summary based on area designations. 
 

CAUTION:  

Use of a high speed torque screwdriver may cause damage to terminal blocks.

 

 
3.1  General

 

 

Connect the field wiring in accordance with the appropriate portion of Figure 1, which illustrates both single- and multiple-
transmitter loops.  
 

 
 
 
 
 
 
The ST5484E transmitter requires a minimum of 11 VDC for proper operation.  This is the minimum voltage required at the 
transmitter (not the power supply), after all other voltage drops across field wiring and receiver input impedance have been 
accounted for with the maximum 20mA of loop current flowing.  The minimum loop power supply voltage required is 
therefore 11 VDC plus 1 volt for each 50 ohms of total loop resistance.   
 

Example:

 

Component 

Resistance 

Signal wiring 

10 ohms 

DC Input Impedance of receiver 

250 ohms 

TOTAL LOOP RESISTANCE 

260 ohms 

 
Minimum supply voltage = 260 (1V/50 ohms) + 11V = 16.2 VDC 
 
The maximum loop power supply voltage that may be applied is 30 VDC.  The maximum loop resistance (R

L

) is calculated by 

the equation: 
 
R

L

 = 50 (V

S

 - 11) ohms 

Example:  
R

L

 = 50 (24 - 11) = 650 ohms for 24 VDC loop supply. 

Figure 1 

Summary of Contents for ST5484E

Page 1: ...nter bore surfacing tool This tool can be used with a portable drill equipped with a magnetic base but care must be taken so that the tapped and threaded hole is perpendicular to the machined surface...

Page 2: ...n This is the minimum voltage required at the transmitter not the power supply after all other voltage drops across field wiring and receiver input impedance have been accounted for with the maximum 2...

Page 3: ...ltage 105 1V 50 ohms 19 1 V 21 2 VDC 3 3 Explosion Proof Installation In Hazardous Locations CSA ST5484E transmitters are CSA certified explosion proof Class I B C D Class II E F G Connect the field w...

Page 4: ...wer supply must be provided Connect the transmitter field wiring using standard instrumentation practices Scaling of the display is on the basis of the range of the transmitter The measurement paramet...

Page 5: ...housings as depicted in Figures 2 The horizontal direction usually incurs more vibration because most machines are more compliant in the horizontal axis than the vertical axis i e the machine s found...

Page 6: ...onduit can be used 7 Calibration The ST5484E transmitter has been factory calibrated for the full scale vibration level marked on the label If the calibration is in doubt the unit can be verified in t...

Page 7: ...nput impedance and they will load this signal resulting in attenuation of as much as 20 to 30 Refer to Table 1 at right showing the nominal attenuation expected for a given input impedance In all case...

Reviews: