Metrix ST5484E Manual Download Page 5

 

 

Document 9162 

Manual - ST5484E 2-Wire Seismic Vibration Transmitter 

Page 5 of 7 

Rev. T (Oct 2013)

 

 

 

Figure 3 

6.  Typical Transmitter Placement 

The ST5484E measures seismic vibration (i.e., vibration velocity) at the 
attachment point on the machine, using engineering units of in/s (inches 
per second) or mm/s (millimeters per second) depending on which ordering 
option has been selected.  The transmitter’s sensitive direction is through 
the long axis of its cylindrical body.  It will not measure side-to-side motion 
 
Typical transmitter mounting for casing vibration measurements is in the 
horizontal direction at the bearing housings as depicted in Figures 2.  The 
horizontal direction usually incurs more vibration because most machines 
are more compliant in the horizontal axis than the vertical axis (i.e., the 
machine’s foundation constrains vertical vibration more than horizontal 
vibration).                                                                              

                                                                                      Figure 2 

 
A horizontal mounting arrangement is also depicted in Figure 3, but with additional detail showing typical accessories. When 
flying leads are ordered, a 24 inch or 72 inch length may be specified using ordering option D.  These leads may be cut to 
length in the field and then spliced to field wiring as shown in Figure 3.   
 

NOTE:

 Hazardous area locations do not allow a splice at the location shown in Figure 3.  Instead, the splice must be made in a 

second conduit hub (meeting splicing requirements) located at the end of flexible conduit.   
 

 

Summary of Contents for ST5484E

Page 1: ...nter bore surfacing tool This tool can be used with a portable drill equipped with a magnetic base but care must be taken so that the tapped and threaded hole is perpendicular to the machined surface...

Page 2: ...n This is the minimum voltage required at the transmitter not the power supply after all other voltage drops across field wiring and receiver input impedance have been accounted for with the maximum 2...

Page 3: ...ltage 105 1V 50 ohms 19 1 V 21 2 VDC 3 3 Explosion Proof Installation In Hazardous Locations CSA ST5484E transmitters are CSA certified explosion proof Class I B C D Class II E F G Connect the field w...

Page 4: ...wer supply must be provided Connect the transmitter field wiring using standard instrumentation practices Scaling of the display is on the basis of the range of the transmitter The measurement paramet...

Page 5: ...housings as depicted in Figures 2 The horizontal direction usually incurs more vibration because most machines are more compliant in the horizontal axis than the vertical axis i e the machine s found...

Page 6: ...onduit can be used 7 Calibration The ST5484E transmitter has been factory calibrated for the full scale vibration level marked on the label If the calibration is in doubt the unit can be verified in t...

Page 7: ...nput impedance and they will load this signal resulting in attenuation of as much as 20 to 30 Refer to Table 1 at right showing the nominal attenuation expected for a given input impedance In all case...

Reviews: