background image

 

 

 

 
 
 
 
 

PAT Demoboard 

MI 3300 

Instruction manual 

Version 1.0.4, Code No. 20 751 070

 

 

 

Summary of Contents for MI 3300

Page 1: ...PAT Demoboard MI 3300 Instruction manual Version 1 0 4 Code No 20 751 070...

Page 2: ...es that the MI 3300 is in compliance with subjected EU directive The full text of the EU declaration of conformity is available at the following internet address http www metrel si DoC 2021 METREL The...

Page 3: ...appliance of class 1 flatiron 9 5 3 Portable appliance of class II receiver 10 5 4 IEC cord 11 5 5 Portable appliance of class 1 extension drum 12 5 6 Portable appliance of class 1 coffee machine 13 5...

Page 4: ...hecked during an electrical equipment safety test can be simulated Error states can be switched On or Off Electrical parameters that can be simulated are Continuity of equipotential bonding Insulation...

Page 5: ...TT outlet The Ready lamp must lit green for normal operation of the Demoboard If red light is blinking and buzzer sounds immediately disconnect the demoboard from the mains and check the supply conne...

Page 6: ...normal operation 5 Electrical equipment simulation area 6 Groove for placing demonstration tables 7 Front plate 8 Manufacturer label 9 Ready indicator Red light demoboard is not ready Blinking red lig...

Page 7: ...ccessible insulated metal part 2 Grounded metal parts 1 2 3 Power ON signal light 4 ON OFF switch 5 Sockets for simulation of various fixed connections 6 Class II mains socket 7 Socket for simulation...

Page 8: ...nly for one fault switched ON at the same time If more than one fault is simultaneously the Error values are summarized Individual demonstration tables are recognized on basis of the information store...

Page 9: ...sulation 500 V DC 20 M 0 106 M Leakage 230 V 50 Hz 0 00 mA 2 17 mA Subleakage 0 00 mA 2 17 mA Error 3 Excessive capacitive current Error value 33 nF L and PE pins on socket 3 Insulation 500 V DC 20 M...

Page 10: ...taken Error off Error on Error 1 Insulation fault Error value 20 M 238 k L pin on socket 2 and accessible isolated metal part 1 Insulation 500V DC probe 20 M 0 238 M Touch Leakage 230 V AC 0 00 mA 0...

Page 11: ...and PE pin on socket 2 Earth Bond 0 02 0 84 Error 2 Insulation fault Error value 20 M 106 k L and PE pins on socket 2 Insulation 500 V DC 20 M 0 106 M Error 3 Crossed L and N wire Polarity L N crosse...

Page 12: ...et 1 and PE connection on mains socket 2 Earth Bond 0 02 0 84 Error 2 Insulation fault Error value 20 M 106 k L and PE pins on socket 1 Insulation 500 V DC 20 M 0 106 M Leakage 230 V 50 Hz 0 00 mA 2 1...

Page 13: ...t 2 Earth Bond 0 02 0 43 Error 2 Insulation fault Error value 20 M 106 k L and PE pins on socket 2 Insulation 500 V DC 20 M 0 106 M Leakage 230 V 50 Hz 0 00 mA 2 17 mA Subleakage 0 00 mA 2 17 mA Error...

Page 14: ...et 2 Earth Bond 0 02 0 84 Error 2 Insulation fault Error value 20 M 106 k L and PE pins on socket 2 Insulation 500 V DC 20 M 0 106 M Leakage 230 V 50 Hz 0 00 mA 2 17 mA Subleakage 0 00 mA 2 17 mA Erro...

Page 15: ...2 Insulation fault Error value 20 M 1 88 M L 3 and PE 4 input connections Insulation 1000 V DC 20 M 1 880 M Withstanding 1000 V AC 0 1 mA 0 6mA Error 3 Excessive charge on filter capacitors Error valu...

Page 16: ...2 0 41 Error 2 Insulation fault Error value 20 M 1 88 M L 2 and PE connection 3 Insulation 1000 V DC 20 M 1 880 M Withstanding 2500 V AC 0 1 mA 1 4 mA Error 3 Excessive charge on filter capacitors Err...

Page 17: ...e only Actual inaccuracy is 10 of given Error values If the outputs of measuring instruments are not galvanically isolated an additional error of up to 10 can occur on instrument s reading 6 2 Content...

Page 18: ...MI 3300 PAT Demoboard Specification 18...

Page 19: ...MI 3300 PAT Demoboard Specification 19...

Page 20: ...MI 3300 PAT Demoboard Specification 20...

Reviews: