7
6. Technical Data
Meter type
MQM Quantometer
Approval
PED 97 / 23 / EC
Size
G 10 to G 1000
Nominal diameter
DN 25 (2“) to DN 150 (6“)
Pressure rating
PN 16 and ANSI CLASS 150
Rangeability
20:1 or higher depending on the operation pressure
Temperature ranges
• gas temperature
-20°C to +60°C
• ambient temperature
-25°C to +55°C
• storage temperature
-25°C to +55°C
Housing material
Aluminum
Max. operation pressure
20 barg
Accuracy
Q
min
≤ Q < Q
t
: ±3.0 %
Q
t
≤ Q ≤ Q
max
: ±1.5 %
Q
t
= 0,2 Q
max
Meter index
Number of indexes
1
Number of digit rollers per index
8
Meter index head
Composite (optional: Aluminum)
Protection class
IP 65
Pulse generators
LF-pulse generator
1 LF (reed contact), add. 1 LF as option
Contact type
make contact (normally open)
Max. contact load
10 W
Max. switching voltage
50 VDC / 200 VDC
Max. switching current
0.1 A / 0.5 A
Resistance
100 Ω in series to reed contact
Max. switching frequency f
max
500 Hz
HF-pulse generator:
1 HF (inductive sensor, acc. NAMUR specs)
Supply voltage
8.2 VDC (internal resistance of 1kΩ)
Current consumption (sensor covered)
< 1 mA
Current consumption (sensor free)
> 2.1 mA
Max. switching frequency f
max
1500 Hz
Anti tampering contact
1 Reed contact in series with 100 Ω resistor
Contact type
make contact (normally closed)
Max. contact load
10 W
Max. switching voltage
175 VDC
Max. switching current
0.25 A
Resistance
100 Ω in series to reed contact