metran MK3071 Installation Instructions Manual Download Page 25

Multi-Function Air To Water Heat Pump

2.Malfunction Indicating Table. Determine and solve the malfunction by

malfunction code as below:

Malfunction and
Protection Name

Reason

Solution

Display
Mode

Cooling/heating inlet water
temp. Sensor failure

Cooling/heating outlet water
temp. Sensor failure

System1coil temp.
Sensor failure

System 2 coil temp.
Sensor failure

Ambient temp. sensor
failure

Solar collector sensor
failure

1.Check whether the connection of sensor is poor.
2.Check or change the solar collector sensor.

1.Check whether the connection of sensor is poor.
2.Check or change the ambient sensor.

1.Check whether the connection of sensor is poor.
2.Check or change the system 2 coil sensor.

1.Check whether the connection of sensor is poor.
2.Check or change the

sensor.

system 1 discharge

The sensor is open
or short circuit

The sensor is open
or short circuit

The sensor is open
or short circuit

The sensor is open
or short circuit

The sensor is open
or short circuit

The sensor is open
or short circuit

The sensor is open
or short circuit

The sensor is open
or short circuit

The sensor is open
or short circuit

1.Check whether the connection of sensor is poor.
2.Check or change the system 1 coil sensor.

1.Check whether the connection of sensor is poor.
2.Check or change the hot water outlet sensor.

1.Check whether the connection of sensor is poor.
2.Check or change the hot water tank sensor.

1.Check whether the connection of sensor is poor.
2.Check or change the air condition outlet sensor.

1.Check whether the connection of sensor is poor.
2.Check or change the air condition inlet sensor.

Hot water tank temp.
Sensor failure

Hot water outlet temp.
Sensor failure

System 1 discharge temp.
Sensor failure

E

00

E

01

E

02

E

03

E

05

E

06

E

07

E

08

E

09

E 10

System 2 discharge temp.
Sensor failure

The sensor is open
or short circuit

1.Check whether the connection of sensor is poor.
2.Check or change the system 2 discharge sensor.

System 2 high pressure
protection

Hot water side water flow
switch failure protection

Air condition side antifreezing
protection in winter

Air condition side frost
protection

System 1 discharge temp
too high protection

Hot water side antifreezing
protection in winter

Auxiliary electric overheating
protection(hot water side)

No water/little water
in water system.

System 1 low pressure
protection.

The unit is not

running well.

System 1 high pressure
protection.

1.Check whether the hor water side flow switch is normal.

2.Check whether the hot water side water system is normal.

System 2 low pressure
protection.

Air condition side water flow
switch failure protection

System 2 discharge temp
too high protection

Auxiliary electric overheating
protection(air condition side)

Phase sequence protection

P00

P 01

P 02

P 03

P 04

P 05

P 06

P 07

P 08

P 09

P 10

P 11

P 12

P 13

P15

Ambient temperature too low
protection

System 1 high pressure
switch is opened

System 1 low pressure
switch is opened

System 2 high pressure
switch is opened

System 2 low pressure
switch is opened

No water/little water
in water system.

Air condition side water
outlet temp. too low

System 1 is not

running well.

System 2 is not

running well.

Ambient temp.
too low.

Overheating protection
switch is open.

Overheating protection
switch is open.

Power supply phase
failure /lacking

Ambient temp.is too
low

1.Check whether the high pressure switch is normal.

2.Check whether the water tank temperature setting is too high.

3.Check whether the refrigerant is over capacity.

1.Check whether the low pressure switch is normal.

2.Check whether refrigerant leak.

1.Check whether the high pressure switch is normal.

2.Check whether the water tank temperature setting is too high.

3.Check whether the refrigerant is over capacity.

1.Check whether the low pressure switch is normal.

2.Check whether refrigerant leak.

1.Check whether the air condition side flow switch is normal.

2.Check whether the air condition side water system is normal.

Check the whether it 's power supply phase failure /lacking or not,

if phase failure ,please exchange the position of phase ,and

power up again.

1.Check whether the hor water side flow switch is normal.

2.Check whether the hot water side water system is normal.

1.Check whether the water tank temperature setting is too high.

2.Check whether the system 1 refrigerant is over capacity.

1.Check whether the water tank temperature setting is too high.

2.Check whether the system 2 refrigerant is over capacity.

1.Check whether the air condition side flow switch is normal.

2.Check whether the air condition side water system is normal.

Defrost

With automatic antifreezing funtion to avoid the unit freezing off.

With automatic antifreezing funtion to avoid the unit freezing off.

With automatic antifreezing funtion to avoid the unit freezing off.

23

Summary of Contents for MK3071

Page 1: ...METRAN MULTI FUNCTION AIR TO WATER HEAT PUMP MULTI FUNCTION AIR TO WATER HEAT PUMP Installation instruction manual CODE MK3075 MK3076 MK3071...

Page 2: ...ys 9 Parameter Table 1 Care and maintenance 2 Malfunction Indicating Table 3 Determine and solve malfunction 1 Double system type electrical box of internal structure 2 MK3071 PCB Power sequence curre...

Page 3: ...is effective If the ground is imperfect may result in personal injury 2 4 Heat pump before testing hot water side and air conditioning side of the water system must be full of water drain pipes befor...

Page 4: ...principle take a small amount of electricity as driving force and refrigerant as carrier an endless absorption the air and water low grade thermal energy which is difficult to use 15 43 change into a...

Page 5: ...H Cooling and hot water CR cooling and heating CHR C heating and hot water ooling Energy exchange medium A Air W Water Z Integrated type W Split type indoor unit P With built in pump without built in...

Page 6: ...50 Scroll 2 2 58 1 1 4 7 8 1 1 4 6 7 1450 730 1260 1545 780 1310 265 290 Rated Heating Capacity Rated Cooling Capacity Hot water side Air condition side Model Rated Output Water Rated Input Power Rat...

Page 7: ...85 470 700 980 525 725 660 660 860 750 700 960 55 70 40 45 45 57 035W P 035A 035B 230 9 0 30800 10 5 35900 3 10 14 1 20 35 220 1 50 Rotary 1 1 1 50 3 8 1 2 1 2 3 600 630 785 710 750 915 885 470 700 98...

Page 8: ...ices when installed refer to the Third installation 3 pipe connection the parameter value is 0 7MPa 2 The water can drain from the pressure relief device in the outlet pipe which should keep connected...

Page 9: ...of split type unit 665 390 600 785 A B C D Size 030W P S 060W P S Units mm MACHRW D C A B 440 525 885 945 A B C D Size 030A 035A Units mm MAFP 440 525 885 1250 040A 045A 050A 060A 440 525 885 700 D A...

Page 10: ...nd shake 2 3 No sunlight to the unit Set an awning if necessary 2 4 The water from rain and defrosting can be discharged in the installation position 2 5 The unit will not be covered by snow in the in...

Page 11: ...ace requirements 4 hot water tank water tank and buffer tank water tank install location select 4 1 The water tank can be installed in the outdoor with heat pump outdoor unit such as balconies roofs f...

Page 12: ...er filter to reduce the water system resistance loss 7 7 The unit air conditioning side and the hot water side which connect to running water must be installed a one way valve filter and pressure reli...

Page 13: ...ameter must ensure that the unit s maximum starting current requirements 9 3 power supply circuit must have a grounding wire which should connect with a reliable external ground wire and the external...

Page 14: ...line of board in the electrical box 9 8 Unit control panel Code MK3075 Fuse specifications 10A 250V 10 Electrical Wire Selection 10 1 Voltage drop occur may due to the large current draw during compr...

Page 15: ...W A B 040Z W A B S 045Z W A B S 050Z W A B S 060Z W A B S 080ZB S 100ZB S 120ZB S 200ZB S 300ZB S 220V 1PH 50Hz 2 5mm 2 mm 2 380V 3PH 50Hz 2 5mm 2 mm 2 4 0mm 2 mm 2 2 5mm 2 mm 2 2 5mm 2 mm 2 2 5mm 2 m...

Page 16: ...n start the hot water side air conditioning side solar side circulating pump opened the exhaust valve again to drain the pipe air observe and listen water pump operation the circulating water flow whe...

Page 17: ...A C water Inlet Hot water tank Solar Collector Ambient temp 2011 04 08 11 25 Off 12 25 25 30 Under the main interface press enter into parameter setting interface choose main menu press button choose...

Page 18: ...the output When the unit while meeting the parameters of 3 1and3 2 The auxiliary heating output Parameter 3 1 Auxiliary electric heater start delay time the time to delay after unit power on the elec...

Page 19: ...ired output Normal the hot water cycle pump not required output Prg Ese Mode A C cool temp Hot water temp H W aux heat Cooling Hot water 12 55 on Cooling Hot water mode Prg Ese Mode Hot water temp Ele...

Page 20: ...r condition side water flow switch Hot water flow switch System 1 high pressure switch System 1 low pressure switch System 2 high pressure switch System 2 low pressure switch Air condition side net sw...

Page 21: ...state condition 1 when the coil temperature is higher than the set value of this parameter the condition is met out defrost state condition 2 when the defrost time is running larger than this paramet...

Page 22: ...ng timing on or off interface press the key to turn options Note Press button for 5 seconds when you hear the beep sound you can see the page to add Timer on and Timer off select column Prg Prg 6 1 Wh...

Page 23: ...water 1 2 A C T 1 3 H W T 3 1 Aux start delay 4 1 Ambient low 4 2 Power remember 4 3 System number 4 4 Priority 4 5 A C pump 4 6 H W pump 4 7 E H A C Pump 4 8 E H H W Pump 4 9 Comp PT temp 15 On 2 H...

Page 24: ...rounding should be clean and dry well ventilated A regular time 1 2 months to clean air side heat exchanger to maintain good heat transfer 1 7 Always check the unit s parts work check units inside pip...

Page 25: ...ter in water system System 1 low pressure protection The unit is not running well System 1 high pressure protection 1 Check whether the hor water side flow switch is normal 2 Check whether the hot wat...

Page 26: ...ystem 2 Change the flow switch 1 Power failures 2 The unit wire loses 3 The unit power fuse burns out 1 The water system is lack of water 2 There s air in the system 3 The water system valve doesn t o...

Page 27: ...ion hot water cycle pump Connection solar cycle pump Connection air conditioner aux electric Connection hot water aux Electric Air condition side net switch Mode switch effective for disconnect the wi...

Page 28: ...1122 E VALVE1 E VALVE2 01 02 03 04 05 06 07 08 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 TRAN IN CN1 CN2 CN3 CN2 GND Hot water tank temp GND Ambient temp GND System1 disc...

Page 29: ...acitance Fan Red Orange Capacitance Black White Black White A B C D E F G H 10A 250V 23 Red Blue White Red Blue Red Blue White Blue Red Red Blue White Red Red Red Black White Blue Red Red Red Red Red...

Page 30: ...ve Glass thermometer Y graph filter 1 Hot water tank 2 Controller 3 Unit Expansion Tank 4 5 Buffer tank 6 Water distribution device 7 Water collection device Fan coil 14 Water to waterexchanger 15 Swi...

Page 31: ...ylinder filter 18 Replenishment water inlet 19 8 Solar 9 Solar cycle pump 13 Radiators Supply hot water pump 10 Bath room 11 Floor heating coil 12 Pressure gauge Flexible connectors Globe valves Elect...

Page 32: ......

Page 33: ......

Page 34: ......

Page 35: ......

Page 36: ......

Reviews: