background image

TWRF1 SCR Power Controller 

 

Operation 

Rev 2 

Ametek HDR Power Systems 

13 

 

Figure 3.3  Process Controller Input Connections 

 

d.  Adjust the 

ZERO

 control CW until the output just turns on, then turn the 

ZERO

 control CCW just to 

the point where the output voltage reading is zero. 

e.  Set  the  CUR/PWR  potentiometer  or  Process  controller  to  demand  100%  output.    Observing  the 

voltmeter,  adjust 

SPAN

  CW  just  to  the  point  where  the  reading  is  below  the  maximum  output 

voltage.  Then adjust 

SPAN

 CW just to the point where the meter reading is at maximum. 

f.  Repeat steps 3.3e and 3.3f as necessary, to ensure proper control adjustments have been made. 

g.  Turn  off  the  line  power  to  the  TWRF1  and  disconnect  the  test  equipment.    The  TWRF1  is  now 

ready for automatic operation. 

h.  Adjust the 

CUR/PWR

 potentiometer CW until the output trips to the desired level.   

3.5 

Auto/Manual Control with a Controller and Remote Potentiometer 

On closed loop processes it may be desirable to be able to operate the unit manually. The SCR Power 
Controller has this capability designed into it. Connect the Command Signal, a Remote Manual control 
and  an  Auto/Manual  switch  in  the  Auto  position.  By  switching  to  the  Manual  position,  the  Remote 
Manual control operates and the auto signal is disconnected.  
 
With the power to the TWRF1 turned off, connect the switch, potentiometer, and controller as shown in 
Figure 3.4 and remove jumper from terminal TB1-7 and TB1-8.  Install the 

AUTO/MAN

 switch in the 

same  general  location  as  the  remote  manual  potentiometer.    Note  that  the  full  CW  position  of  the 
potentiometer is the full-power-output position. 
 

 

 

Figure 3.4  Auto/Man Control with Controller and Remote Potentiometer 

 
Place the 

AUTO/MAN 

switch  to 

AUTO

  and  calibrate  the  system  as  described  in  steps 3.3b through 

3.3h. 

Summary of Contents for TWRF1 SCR Series

Page 1: ...tion and Maintenance Manual Number 9100051 Revision 2 530 Lakeview Plaza Blvd Ste C Worthington Ohio USA 43085 Toll Free 1 888 PWR CNTL 797 2685 Phone 614 308 5500 Fax 614 308 5506 Web www hdrpower co...

Page 2: ...presentative nearest you please call Ametek HDR Power Systems main office at 614 308 5500 Revision 1 December 2017 Initial Release Revision 2 Aug 2022 General Revision 2022 by Ametek HDR Power Systems...

Page 3: ...mote Manual Control with a Potentiometer 11 3 4 Process Command Input Control 12 3 5 Auto Manual Control with a Controller and Remote Potentiometer 13 3 6 On Off Control 14 3 7 Shutdown 14 3 8 Overcur...

Page 4: ...wer Controller ii Ametek HDR Power Systems Rev 2 7 1 Warranty 24 7 2 In house Repair Services 24 7 3 Field Service Repairs 25 APPENDIX 26 Appendix A System Schematic 26 Appendix B 30 60 A Outline 27 A...

Page 5: ...ut Connections 13 Figure 3 4 Auto Man Control with Controller and Remote Potentiometer 13 Figure 3 5 On Off Control 14 Figure 3 6 Shutdown Control 14 Figure 3 7 Current Limit Trip Board 15 Figure 4 1...

Page 6: ...Table of Contents TWRF1 SCR Power Controller iv Ametek HDR Power Systems Rev 2...

Page 7: ...anch circuit fused disconnect or circuit breaker with this Power Controller is required to ensure the safety of operating personnel CAUTION HAZARDOUS VOLTAGES exist at the Power Controller Load AT ALL...

Page 8: ...Safety Instructions TWRF1 SCR Power Controller 2 Ametek HDR Power Systems Rev 2...

Page 9: ...the SCRs is controlled by a digital firing control circuit synchronized in phase with line frequency either 50 or 60 Hz A soft start approximately a 1 cycle ramp feature is standard that allows the Po...

Page 10: ...ch the output can increase to prevent high inrush currents with transformer coupled loads or high cold to hot resistance ratios such as tungsten heating elements The rate of increase is limited to app...

Page 11: ...red Power output linearity versus control signals input 2 Non isolated 5 Isolated Power SCRs protection Current surge Subcycle I T semiconductor fuse OPTIONAL Transient voltage spikes dv dt Metal Oxid...

Page 12: ...Description TWRF1 SCR Power Controller 6 Ametek HDR Power Systems Rev 2...

Page 13: ...15 30 A and 10 AWG or larger wire for the other sizes NOTICE Use copper conductors rated 75 C minimum for all model current ratings On the internal side of the TWRF1 the wire from L2 should connect to...

Page 14: ...nal Input HDR s TWRF Phase Fired SCR Power Controllers are configured for a potentiometer non isolated but has the capability of having either an isolated current or non isolated voltage Command Signa...

Page 15: ...cedure as follows 1 Open the SCR power controller and locate transformer T1 The primary side of T1 transformer will contain two wires one black the other white and black Refer to figure 2 3 Figure 2 3...

Page 16: ...Operation TWRF1 SCR Power Controller 10 Ametek HDR Power Systems Rev 2...

Page 17: ...icator The Command Signal Indicator is a green Light Emitting Diode LED located on the front cover of the unit The brilliance of this LED will change with a current Command Signal The brilliance incre...

Page 18: ...ge reading is at maximum h If necessary readjust ZERO with remote potentiometer fully CCW and SPAN control and remote potentiometer fully CW i Turn off the line power to the TWRF1 and disconnect the t...

Page 19: ...eter CW until the output trips to the desired level 3 5 Auto Manual Control with a Controller and Remote Potentiometer On closed loop processes it may be desirable to be able to operate the unit manua...

Page 20: ...enable the TWRF1 Figure 3 5 On Off Control Calibrate the system by performing the steps in 3 3 Note that zero power demand is accomplished by opening the contacts with the controller and maximum powe...

Page 21: ...Adjust the OC CUR PWR potentiometer fully CW b With the power controller at full output adjust OC CUR PWR potentiometer CCW until the unit shuts off c Adjust the OC CUR PWR potentiometer slightly CW d...

Page 22: ...Operation TWRF1 SCR Power Controller 16 Ametek HDR Power Systems Rev 2...

Page 23: ...ing of the SCRs is controlled by a digital firing control circuit synchronized to the line frequency 50 or 60 Hz The firing control circuit may be manually controlled by the built in ZERO control or a...

Page 24: ...rnal control device From midpoint to extreme CW is the positive control region whose extremes correspond to 0 and 100 power output respectively as manually adjusted The SPAN control is used as a final...

Page 25: ...riable from zero to some intermediate value but cannot be brought to maximum The symptoms listed may be caused by one or more of the following an environmental problem faulty input power or load conne...

Page 26: ...ns should be free of dust or dirt for proper heat transfer and free of obstructions which could prevent proper airflow Contamination The unit should be periodically cleaned of all dust and dirt Howeve...

Page 27: ...n the Rx1 scale the resistance should be infinite in both directions If a shorted component is indicated in any of these cases replace it 2b Firing control section defective Replace the fuse and retur...

Page 28: ...rrange for service at your site or by shipment to Ametek HDR Power System as you request We will make every possible attempt to support your emergency on site needs regardless of how contacted 6 2 Spa...

Page 29: ...0 2087000 2099112 6791114 1 1 1 1 60 Ampere Units PCB Assy PF1 Extended Gate PCB Assy Over current Trip PCB Assy DVDT SCR dual pkg 1622 A 1400 V 2099160 2087000 2099112 6722114 1 1 1 1 90 Ampere Units...

Page 30: ...Y OR OTHERWISE IN NO EVENT WILL AMETEK HDR BE LIABLE FOR INCIDENT OR CONSEQUENTIAL DAMAGES NOR IN ANY EVENT SHALL HDR S LIABILITY EXCEED THE UNIT PRICE OF ANY DEFECTIVE PRODUCT OR PART 7 2 In house Re...

Page 31: ...Power Systems 25 7 3 Field Service Repairs Repairs may be performed at your location Please contact Ametek HDR Power Systems at 614 308 5500 to discuss terms and conditions to get the current service...

Page 32: ...Warranty TWRF1 SCR Power Controller 26 Ametek HDR Power Systems Rev 2 APPENDIX Appendix A System Schematic Note Thermostat and fan not included on 60 A and smaller models...

Page 33: ...TWRF1 SCR Power Controller Appendix Rev 2 Ametek HDR Power Systems 27 Appendix B 30 60 A Outline R...

Page 34: ...Warranty TWRF1 SCR Power Controller 28 Ametek HDR Power Systems Rev 2 Appendix C 90 225 A Outline R...

Page 35: ...Notes...

Page 36: ...530 Lakeview Plaza Blvd Ste C Worthington Ohio 43085 USA...

Reviews: