22 Control Modules—Network Control Module 200 Series
Attaching to either the NCM’s RS-232 submodule or RS-232 port is a
special right-angle cable with narrow profile shell (NU-CBL101-0). The
user connects the pigtailed wires of this cable into a separately ordered
hood, male (MHK101) or female (FHK101), according to the pinout
requirements of the user’s device. The wire configuration of
NU-CBL101-0 is diagrammed in Figure 8.
200TC06
Shield (FG)
Brown
Red
Orange
Yellow
Green
Blue
Violet
White
Black
NU-CBL101-0
1
2
3
4
5
6
7
8
18
20
Figure 8: Pinouts for NU-CBL101-0
OWS to the NCM RS-232 submodule:
200TC07
Out
Out
In
In
In
In
Out
Out
Out
In
In
In
Out
Out
FG
TD Black
RD Brown
RTS Red
CTS Orange
DSR Yellow
SG Green
DCD Blue
DTR White
NCM RS-232
Submodule
IBM PC Serial Port
(Female, FHK101)
DCE DCD Violet
FG
TD
RD
CTS
RTS
DSR
SG
DCD
DTR
DCE DCD
Shell
1
2
3
4
5
6
7
8
18
20
2
3
4
5
6
7
8
18
20
Figure 9: IBM PC Serial Port of OWS Connected to the
NCM RS-232 Submodule
Right Angle
Cable
Operator
Workstation
Cabling