Conventional Products—2400AT and 2400AIT Direct 2-Wire Smoke Detector 11
Testing and Maintenance
Procedures
Before testing, notify the proper authorities that the smoke detector system
is undergoing maintenance and will be temporarily out of service. Disable
the zone or system undergoing maintenance to prevent unwanted alarms.
Before testing the detector, check for the presence of the flashing LED.
If it does not flash, power has been lost (check the wiring) or it is defective
(return for repair).
Detectors must be tested after installation and periodic maintenance.
After a detector is set into alarm by one of the following test methods, and
the alarm activating device is removed from the detector, the system
should be reset at the control panel before testing any additional detectors.
After all testing is complete, notify the proper authorities the system is
back in service.
Recessed Test Switch
1.
Push and hold the recessed test switch with a 0.1 inch maximum
diameter tool, such as a pocket screwdriver.
2.
The LED on the detector should light and report an alarm condition to
the control panel on the IDC within five seconds.
3.
The piezo horn should also sound.
Calibrated Test Card (R59-18-00)
1.
Remove the detector cover by placing a small-bladed screwdriver in
the side slot of the detector cover.
2.
Twist it slightly until the cover can be turned counterclockwise for
removal.
3.
Insert the NO ALARM end of the test card fully into the test slot
(Figure 7).
4.
Slide it counterclockwise until it stops.
5.
The detector should not alarm (wait at least 20 seconds).
6.
Remove the test card by sliding it clockwise before removing.
7.
Repeat with the ALARM end of the test card.
Testing
Testing the
2400AT and
2400AIT