Conventional Products—2400AT and 2400AIT Direct 2-Wire Smoke Detector 7
Installation Procedures
This section contains installation information for 2400AT and 2400AIT
direct wire smoke detectors. Instructions are given for mounting the
detector, and basic wiring information is provided.
Each 2400 series detector is supplied with a mounting bracket kit that
permits it to be mounted in either of two ways:
●
directly to a 3 inch (76.2 mm) octagonal, 4 inch (101.6 mm)
octagonal, or 1-1/2 inch (38.1 mm) deep electrical box
(Figures 1 and 2)
●
to a 4 inch (101.6 mm) square electrical box using a plaster ring with
the mounting bracket kit supplied
flmount2
Figure 1: Flush Mounting of Detector on 4 Inch Octagonal Box
Tamper
Resistant Tab
mountbrk
To make detector tamper-proof,
break off tab extension at scribed line.
Figure 2: Detector Mounting Bracket
General
Information
Mounting