14.2 Honeywell ESYS
–
black remote control
The fireplace is controlled by means of a bidirectional communication between the RF remote control and the
receiver. Thanks to this, error messages can be displayed on the screen of the remote control.
14.2.1 Examples of error messages:
Communication failure between RF remote control and the fireplace.
The triangle symbol blinks.
Possibly the distance between the fireplace and the remote control is too large. Bring
the remote control closer to the fireplace.
Failure of the fireplace. On the screen, an F followed by a 2-figure failure code is visible.
The triangle symbol blinks.
The hourglass symbol becomes visible as soon as a lock-out failure has been
reset by means of both scroll arrows. As soon as the fireplace has been reset,
the basic screen appears again on the remote control.
A lock-out failure of the fireplace. On the screen, an F followed by a 2-figure failure
code is visible. The triangle symbol blinks.
The “reset” message indicates that
the
fireplace can be reset.
This can be done by pressing both scroll arrows simultaneously.
Failure of the temperature sensor of the RF remote control.
Automatic switch-over to manual operation and flame height setting.